7.3 Standard Configuration Devices Wiring

7.3
Standard Configuration Devices Wiring
Install the standard configuration devices according to
For more information, refer to
standard configuration devices.
Voltage Class
Model
Harmonic Filter Module
Input-side AC Reactor 1
Input-side AC Reactor 2
Reactor for Harmonic Filter
Capacitor for Harmonic Filter
Voltage Class
Model
Harmonic Filter Module
Input-side AC Reactor 1
Input-side AC Reactor 2
Reactor for Harmonic Filter
Capacitor for Harmonic Filter
◆ Wire Gauges and Tightening Torque
Use the tables in this section to select the appropriate wires and crimp terminals.
Note: 1. Wire gauge recommendations based on continuous current ratings using 75°C 600 Vac vinyl-sheathed wire assuming ambient
temperature within 40°C.
2. Wire gauge recommendations for models 4A0270 to 4A0630 based on continuous current ratings using 105°C 600 Vac vinyl sheathed
wire assuming ambient temperature within 40°C.
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is
greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following
formula to calculate the amount of voltage drop:
Line drop voltage (V) =
Harmonic Filter Module
Refer to
Wire Gauges and Tightening Torque on page 59
Input-side AC Reactor 1
Recommended
CIMR-D
Terminals
U, V, W
2A0005
X, Y, Z
U, V, W
2A0010
X, Y, Z
162
Standard Connection Diagram on page
Table 7.2 Standard Configuration Devices (200 V Class)
2A0005
2A0010
Table 7.3 Standard Configuration Devices (400 V Class)
4A0005 4A0010 4A0020 4A0030 4A0040 4A0060 4A0100 4A0130 4A0185 4A0270 4A0370 4A0630
× wire resistance (Ω/km) × wire length (m) × current (A) × 10
3
Table 7.4 Wire Gauge and Torque Specifications
For Asia
<1>
Applicable
Recommended
Gauge
Gauge
2
2
mm
mm
AWG, kcmil
2
2 to 5.5
5.5
5.5 to 14
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
Table 7.2
and
Table 7.3
44. Refer to the product catalog for selection of
200 V Class
2A0020
2A0030
2A0050
400 V Class
when wiring of the harmonic filter module.
For U.S.A.
For Europe and China
<2>
Applicable
Recommended
Gauge
Gauge
AWG,
kcmil
200 V Class
12
12 to 10
8
8 to 6
when installing the converter.
2A0065
2A0090
-3
<3>
Screw
Applicable
Gauge
Gauge
2
2
mm
mm
4
4 to 6
4
4 to 16
2A0130
Tightening
Torque
Size
N m
(lb in.)
1.0 to 1.3
M4
(8.9 to 11.5)
2.0 to 2.5
M5
(17.7 to 22.1)

Advertisement