YASKAWA D1000 Series Instruction Manual page 191

Type cimr-du/power regenerative converter 200 v class, three-phase input: 5 to 130 kw/400 v class, three-phase input: 5 to 630 kw
Hide thumbs Also See for D1000 Series:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
U1-61
Active Current
(108AH)
U1-62
Reactive Current
(108BH)
DC Bus Voltage
U1-63
Reference (After
(108CH)
SFS)
Avr Input
U1-64
(Voltage
(108DH)
Deviation)
U1-65
Avr Output
(108EH)
U1-66
Control Voltage
(108FH)
Reference (Vq)
U1-67
Control Voltage
(1090H)
Reference (Vd)
Input Power
U1-72
Supply
(1095H)
Information
U2-01
Current Fault
(80H)
U2-02
Previous Fault
(81H)
Input Terminal
U2-11
Status at Previous
(8AH)
Fault
Output Terminal
U2-12
Status at Previous
(8BH)
Fault
Drive Operation
U2-13
Status at Previous
(8CH)
Fault
Cumulative
U2-14
Operation Time at
(8DH)
Previous Fault
Heatsink
U2-20
Temperature at
(8EH)
Previous Fault
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
LCD
Display
Active
Shows the active current.
Current
Reactive
Shows the reactive current.
Current
DC Volt
Shows the DC bus voltage reference after the soft starter.
SFS Out
AVR Input Shows the Avr input.
AVR
Shows the Avr output.
Output
Voltage Ref
Shows the control voltage reference (Vq) in the converter for the current
(Vq)
control on the power supply side.
Voltage Ref
Shows the control voltage reference (Vd) in the converter for the current
(Vd)
control on the power supply side.
Shows information on the input power supply.
U1 - 72=
0 0 0 0 0 0 0 0
AC Supply
Status
U2: Fault Trace
Current
Displays the current fault.
Fault
Last Fault
Displays the previous fault.
Input Term
Displays the input terminal status at the previous fault. Displayed as in
Sts
U1-10.
Output
Displays the output status at the previous fault. Displays the same status
Term Sts
displayed in U1-11.
Inverter
Displays the operation status of the converter at the previous fault.
Status
Displays the same status displayed in U1-12.
Elapsed
Displays the cumulative operation time at the previous fault.
time
Actual Fin
Displays the temperature of the heatsink when the most recent fault
Temp
occurred.
Description
Bit 0: AUv reset. (0: Not completed, 1: Reset)
Bit 1: PF3 reset (0: Not completed, 1: Reset)
Bit 2: Rated frequency detection
(0: Not completed, 1: Completed)
Bit 3: Phase order detection
(0: Not completed, 1: Completed)
Bit 4: Power supply established
(0: Not completed, 1: Completed)
Bit 5: Fdv detection (0: Not detected, 1: Detected)
Bit 6: PF3 detection (0: Not detected, 1: Detected)
Bit 7: Reserved.
B.2 Parameter Tables
Analog
Output
Unit
Level
10 V: 100.0%
0.1%
10 V: 100.0%
0.1%
200 V Class
10 V: 400 V
1 V
400 V Class
10 V: 800 V
200 V Class
10 V: 400 V
1 V
400 V Class
10 V: 800 V
10 V: 100.0%
0.01%
200 V Class
10 V: 200 V
1 V
400 V Class
10 V: 400 V
200 V Class
10 V: 200 V
1 V
400 V Class
10 V: 400 V
No signal
output
available
No signal
output
available
1 h
1°C
191
B