Alarm And Error Displays - YASKAWA D1000 Series Instruction Manual

Type cimr-du/power regenerative converter 200 v class, three-phase input: 5 to 130 kw/400 v class, three-phase input: 5 to 630 kw
Hide thumbs Also See for D1000 Series:
Table of Contents

Advertisement

◆ Alarm and Error Displays

Faults
Table 5.2
gives an overview of possible fault codes. Conditions such as overvoltages can trip faults and alarms. It is
important to distinguish between faults and alarms to determine the proper corrective actions. When the converter detects
a fault, the ALM indicator LED lights, the fault code appears on the digital operator, and the fault contact MA-MB-MC
triggers. An alarm is present if the ALM LED blinks and the fault code on the digital operator flashes. Refer to
Faults and Alarms on page 104
Digital Operator
Display
LED
LCD
Aov
Power Supply Overvoltage
AUv
Power Supply Undervoltage
bUS
Option Communication Error
MEMOBUS/Modbus
CE
Communication Error
CoF
Current Offset Fault
CPF00,
,
Control Circuit Error
CPF01
CPF02
A/D Conversion Error
Control Board Connection
CPF03
Error
CPF06
EEPROM Memory Data Error
Terminal Board Connection
CPF07
Error
Terminal Board Connection
CPF08
Error
,
CPF11 to
Control Circuit Error
CPF22
<1>
Control Board Connection
CPF23
Error
CPF24
Converter Unit Signal Fault
CPF26
to
to
Control Circuit Error
CPF35
MECHATROLINK-II
E5
Watchdog Timer Error
EF0
Option Card External Fault
EF1
External Fault
to
to
(input terminal S1 to S8)
EF8
Err
EEPROM Write Error
FAn
Internal Fan Fault
Fdv
Power Supply Frequency Fault
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
for a list of alarm codes.
Table 5.2 Fault Displays
Name
Page
106
106
106
107
107
107
107
108
108
108
108
107
108
108
107
108
109
109
109
109
110
5.1 Alarms, Faults, and Errors
Digital Operator
Display
LED
LCD
FUA
AC Fuse Blowout
FUd
DC Fuse Blowout
GF
Ground Fault
nSE
Node Setup Error
oC
Overcurrent
oFA00 to
Option Card Connection Error
to
oFA43
(CN5-A)
oFb00 to
Option Card Fault (CN5-B)
to
oFb17
oFC00 to
Option Card Fault (CN5-C)
to
oFC55
oH
Heatsink Overheat
oH1
Heatsink Overheat
oL2
Converter Overload
oPr
Operator Connection Fault
ov
Overvoltage
PF2
Input Power Supply Fault
PF3
Input Phase Loss Detection
IGBT Short Circuit or Ground
SC
Fault
SrC
Phase Order Fault
Uv1
Main Circuit Undervoltage
Control Power Supply
Uv2
Undervoltage
Uv3
Soft Charge Circuit Fault
vrE
Resonance Detection
Minor
Name
Page
110
110
110
110
111
111
112
113
113
114
114
114
114
115
115
115
115
116
116
116
117
103