YASKAWA D1000 Series Instruction Manual page 182

Type cimr-du/power regenerative converter 200 v class, three-phase input: 5 to 130 kw/400 v class, three-phase input: 5 to 630 kw
Hide thumbs Also See for D1000 Series:
Table of Contents

Advertisement

B.2 Parameter Tables
H2-
Function
Setting
10
Minor fault
11
Fault reset command active
12
Timer output
1B
During baseblock (N.C.)
1D
During Regeneration
1E
Restart enabled
20
Drive overheat pre-alarm (oH) OH Prealarm
24
Fuse Blowout Detection
25
During Run 1
26
During MC ON
Converter Overload Warning
27
(oL2)
2F
Maintenance Period
30
During torque limit
3B
Alarm 2
3C
LOCAL/REMOTE status
4D
oH Pre-alarm time limit
60
Internal cooling fan alarm
Function 0 to 60 with inverse
100 to 160
output
No.
(Addr.
Name
Hex)
H3-01
Terminal A1 Signal
(410H)
Level Selection
H3-02
Terminal A1
(434H)
Function Selection
H3-03
Terminal A1 Gain
(411H)
Setting
H3-04
Terminal A1 Bias
(412H)
Setting
H3-05
Terminal A3 Signal
(413H)
Level Selection
H3-06
Terminal A3
(414H)
Function Selection
182
H2 Multi-Function Relay Output Settings
LCD Display
Minor Fault
Reset Cmd Active
Timer Output
BaseBlk 2
Regenerating
Dur Flt Restart
FUA/FUD Detect
During RUN 1
MC On
OL2 Pre-alarm
Maintenance
Torque Limit
Minor Fault 2
Local
OH Pre-Alarm
Fan Alrm Det
LCD Display
H3: Multi-Function Analog Inputs
Term A1 Level
0: 0 to 10 V
0: 0-10V, (LowLim=0)
1: -10 to 10 V
1: 0-10V, (BipolRef)
Term A1 FuncSel
Sets the function of terminal A1.
Sets the level of the input value selected in H3-02 when 10
Terminal A1 Gain
V is input at terminal A1.
Sets the level of the input value selected in H3-02 when 0
Terminal A1 Bias
V is input at terminal A1.
Term A3 Signal
0: 0 to 10 V
0: 0-10V (LowLim=0)
1: -10 to 10 V
1: 0-10V (BipolRef)
Terminal A3 Sel
Sets the function of terminal A3.
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
Description
Closed: An alarm has been triggered.
Closed: A command has been entered to clear a fault via the input
terminals or from the serial network.
Closed: Timer output.
Open: Converter has entered the baseblock state (no output voltage).
Closed: Motor is regenerating energy into the converter.
Closed: An automatic restart is performed
Closed: Heatsink temperature exceeds the parameter L8-02 value.
Closed: Fuse burnout detected.
Closed: The drive is ready to operate.
Closed: The magnetic contactor is closed.
Closed: There is an overload warning.
Closed: It is time to perform maintenance on the cooling fan, electrolytic
capacitor, and inrush prevention relay.
Closed: When the torque limit has been reached.
Closed: Alarm occurred (excluding Uv, AUv, Fdv, SrC, and PAUv).
Note: This setting is available in converter software versions
PRG:902003 or later.
Open: REMOTE
Closed: LOCAL
Closed: oH pre-alarm time limit has passed.
Closed: Internal cooling fan alarm
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1
specific function.
Description
to reverse the output signal of that
Values
Default: 0
Min.: 0
Max.: 1
Default: F
Min.: F
Max.: 19
Default: 100.0%
Min.: -999.9%
Max.: 999.9%
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
Default: 0
Min.: 0
Max.: 1
Default: F
Min.: F
Max.: 19

Advertisement

Table of Contents
loading

Table of Contents