3.1 Standard Connection Diagram

3.1
Standard Connection Diagram
Connect the converter and peripheral devices as shown in
Figure 3.1
and
Figure
3.2. It is possible to set and run the
converter via the digital operator without connecting digital I/O wiring. This section does not discuss converter operation;
Refer to
Start-Up Programming & Operation on page 83
for instructions on operating the converter. Refer to
A1000
Connection Example on page 92
for connection with a drive.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before
energizing the converter. Failure to comply could result in death or serious injury from moving equipment.
NOTICE: If unsuitable wiring is performed, the converter could be damaged. Implement protection for branches and short-circuits
according to all national and local standards.
NOTICE: Do not connect AC control circuit ground to converter enclosure. Improper grounding can cause control circuit malfunction.
NOTICE: The minimum load for the relay outputs M1-M2, M3-M4, M5-M6 and MA-MB-MC is 10 mA.
44
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual