Digital Operator
Minor Fault Name
Display
Option Communication
bUS
Cause
Connection is broken or master controller
stopped communicating.
Option is damaged.
The option is not properly connected to the
converter.
A data error occurred due to noise.
Digital Operator
Minor Fault Name
Display
Serial Communication
CALL
Transmission Error
Cause
Communications wiring is faulty, there is a
short circuit, or something is not connected
properly.
Programming error on the master side.
Communications circuitry is damaged.
Termination resistor setting is incorrect.
Digital Operator
Minor Fault Name
Display
MEMOBUS/Modbus
CE
Communication Error
Cause
A data error occurred due to noise.
Communication protocol is incompatible.
The CE detection time (H5-09) is set shorter
than the time required for a communication
cycle to take place.
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
• The connection was lost after initial communication was established.
• Assign a Run command frequency reference to the option.
Error
• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.
If there are no problems with the wiring and the fault continues to occur, replace the option.
• The connector pins on the option are not properly lined up with the connector pins on the
converter.
• Reinstall the option.
• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines and ground
wiring.
• Try to reduce noise on the controller side.
• Use surge absorbers on magnetic contactors or other equipment causing the disturbance.
• Use recommended cables or some other type of shielded line. Ground the shield to the
controller side or on the input power side.
• Separate the wiring for communication devices from the converter input power lines. Install an
EMC noise filter to the converter input power.
Communication has not yet been established.
• Check for wiring errors.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.
Check communications at start-up and correct programming errors.
• Perform a self-diagnostics check.
• If the problem continues, replace either the control board or the entire converter. For
instructions on replacing the control board, contact Yaskawa or your nearest sales representative.
Install a termination resistor at both ends of a communication line. Set the internal termination
resistor switch correctly on slave converters. Place DIP switch S2 to the ON position.
Control data was not received correctly for two seconds.
• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines, and ground
wiring.
• Reduce noise on the controller side.
• Use surge absorbers for the magnetic contactors or other components that may be causing the
disturbance.
• Use only recommended shielded line. Ground the shield on the controller side or on the
converter input power side.
• Separate all wiring for communication devices from converter input power lines. Install an
EMC noise filter to the converter input power supply.
• Check the H5 parameter settings and the protocol setting in the controller.
• Ensure settings are compatible.
• Check the PLC.
• Change the software settings in the PLC.
• Set a longer CE detection time using parameter H5-09.
5.3 Alarm Detection
Detail
Possible Solutions
Detail
Possible Solutions
Detail
Possible Solutions
Alarm
Output
(H2-
=10)
YES
Alarm
Output
(H2-
=10)
YES
Alarm
Output
(H2-
=10)
YES
5
119