Digital Operator
Error Name
Display
Terminal Board
oPE04
Mismatch Error
Cause
The converter was replaced (but the removable
terminal block with parameter backup was not
replaced).
The removable terminal block with parameter
backup was replaced.
Digital Operator
Error Name
Display
Run Command
oPE05
Selection Error
Cause
The Run command is assigned to an option card
(b1-18 = 3) and an input option card is not
connected to the converter.
The Run command is assigned to an option card
(b1-02 = 3) and an input option card is not
connected to the converter.
Digital Operator
Error Name
Display
Multi-Function Analog
oPE07
Input Selection Error
Cause
At least two of these parameters have the same
setting: H3-02, H3-10, or H3-06.
Digital Operator
Error Name
Display
Incorrect Input Voltage
oPE30
Adjustment
Cause
• The setting of o2-04 (Drive Model Selection)
changed.
• ERPROM failed for the input voltage offset.
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
The converter or the removable terminal block with parameter backup was replaced.
Set A1-03 to 5550 to load the parameter settings stored in the terminal board to the converter.
Initialize parameters after converter replacement by setting A1-03 to 2220.
The settings for the Run Command or Bus Voltage Command are not correct.
Reconnect the input option card to the converter.
A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, or H3-06.
Change the settings to H3-02, H3-10, and H3-06 so that functions no longer conflict.
Note: Both 1F (Through mode) and F (Through mode) can be set to H3-02, H3-10, or H3-06
simultaneously.
The input voltage offset adjustment has not been performed.
For information on clearing the fault, consult with your Yaskawa representative or the nearest
Yaskawa sales office.
5.4 Operator Programming Errors
Detail
Possible Solutions
Detail
Possible Solutions
Detail
Possible Solutions
Detail
Possible Solutions
5
127

Advertisement

Table of Contents
loading