3.6 Main Circuit Wiring

3.6
Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit
in the converter.
NOTICE: Do not solder the ends of wire connections to the converter. Soldered wiring connections can loosen over time. Improper
wiring practices could result in converter malfunction due to loose terminal connections.
◆ Main Circuit Terminal Functions
Terminal
200 V
Class
Model
400 V
Class
R/L1
S/L2
T/L3
r1/ 11
Power supply voltage detection inputs
1/ 21
t1/ 31
+
◆ Protecting Main Circuit Terminals
Insulation Caps or Sleeves
Use insulation caps or sleeves when wiring the converter with crimp terminals. Take particular care to ensure that the
wiring does not touch nearby terminals or the surrounding case.
Insulation Barrier
Insulation barriers are packaged with models 4A0270 to 4A0630 to provide added protection between terminals.
Yaskawa recommends using the provided insulation barriers to ensure proper wiring. Refer to
Figure 3.26
for instructions on placement of the insulation barriers.
58
Table 3.2 Main Circuit Terminal Functions
Type
2A0005 to 2A0130
4A0005 to 4A0630
Main circuit power supply input
DC voltage output
For 200 V class: 100 Ω or less
For 400 V class: 10 Ω or less
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
Function
These are the power supply input terminals that connect to
the input reactor.
These terminals are to detect the power supply voltage order
and voltage levels.
These terminals output a DC voltage
Grounding terminal
Page
44
44
64
Figure 3.25