YASKAWA D1000 Series Instruction Manual page 109

Type cimr-du/power regenerative converter 200 v class, three-phase input: 5 to 130 kw/400 v class, three-phase input: 5 to 630 kw
Hide thumbs Also See for D1000 Series:
Table of Contents

Advertisement

Digital Operator
Fault Name
Display
Option Card External
EF0
Cause
An external fault was received from the PLC
and F6-03 is set to a value other than 3.
Problem with the PLC program
Digital Operator
Fault Name
Display
External Fault
EF1
(input terminal S1)
External Fault
EF2
(input terminal S2)
External Fault
EF3
(input terminal S3)
External Fault
EF4
(input terminal S4)
External Fault
EF5
(input terminal S5)
External Fault
EF6
(input terminal S6)
External Fault
EF7
(input terminal S7)
External Fault
EF8
(input terminal S8)
Cause
An external device tripped an alarm function
Wiring is incorrect
Multi-function contact input setting is incorrect
Digital Operator
Fault Name
Display
Err
EEPROM Write Error Data cannot be written to the EEPROM
Cause
Electrical noise has corrupted data while
writing to the EEPROM
Hardware problem
Digital Operator
Fault Name
Display
Internal Fan Fault
FAn
Cause
Internal cooling fan has malfunctioned
Fault detected in the internal cooling fan or
magnetic contactor to the power supply.
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
An external fault condition is present.
Fault
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
Check the PLC program and correct problems.
External fault at multi-function input terminal S1.
External fault at multi-function input terminal S2.
External fault at multi-function input terminal S3.
External fault at multi-function input terminal S4.
External fault at multi-function input terminal S5.
External fault at multi-function input terminal S6.
External fault at multi-function input terminal S7.
External fault at multi-function input terminal S8.
Remove the cause of the external fault and reset the fault.
• Properly connect the signal lines to the terminals assigned for external fault detection
(H1-
= 20 to 2B).
• Reconnect the signal line.
• Check for unused terminals set for H1-
• Change the terminal settings.
• Press "ENTER" on the digital operator.
• Correct the parameter setting.
• Cycle power to the converter.
If the problem continues, replace the control board or the entire converter. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
Fan or magnetic contactor failure
• Cycle power to the converter.
• Check for fan operation.
• Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative
operation time of the fan maintenance timer with U4-04.
• If the cooling fan has exceeded its expected performance life or is damaged in any other way,
follow the replacement instructions in
Details
Possible Solution
Details
Possible Solution
= 20 to 2B (External Fault).
Details
Possible Solution
Details
Possible Solution
Cooling Fans on page
137.
5.2 Fault Detection
5
109