H: Multi-Function Terminals - YASKAWA D1000 Series Instruction Manual

Type cimr-du/power regenerative converter 200 v class, three-phase input: 5 to 130 kw/400 v class, three-phase input: 5 to 630 kw
Hide thumbs Also See for D1000 Series:
Table of Contents

Advertisement

B.2 Parameter Tables

◆ H: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.
No.
(Addr.
Name
Hex)
Multi-Function
H1-01
Digital Input
(438H)
Terminal S1
Function Selection
Multi-Function
H1-02
Digital Input
(439H)
Terminal S2
Function Selection
Multi-Function
H1-03
Digital Input
(400H)
Terminal S3
Function Selection
Multi-Function
H1-04
Digital Input
(401H)
Terminal S4
Function Selection
Multi-Function
H1-05
Digital Input
(402H)
Terminal S5
Function Selection
Multi-Function
H1-06
Digital Input
(403H)
Terminal S6
Function Selection
Multi-Function
H1-07
Digital Input
(404H)
Terminal S7
Function Selection
Multi-Function
H1-08
Digital Input
(405H)
Terminal S8
Function Selection
H1-
Function
Setting
1
LOCAL/REMOTE selection
8
Baseblock command (N.O.)
9
Baseblock command (N.C.)
C
Analog terminal input selection Term A2 Enable
F
Through mode
14
Fault reset
18
Timer function input
180
LCD Display
H1: Multi-Function Digital Inputs
Term S1 Func Sel
Term S2 Func Sel
Term S3 Func Sel
Term S4 Func Sel
Assigns a function to the multi-function digital inputs S1
to S8.
Note: Set unused terminals to F.
Term S5 Func Sel
Term S6 Func Sel
Term S7 Func Sel
Term S8 Func Sel
H1 Multi-Function Digital Input Selections
LCD Display
Local/Remote Sel
Ext BaseBlk N.O.
Ext BaseBlk N.C.
Term Not Used
Fault Reset
Timer function
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
Description
Description
Open: REMOTE (parameter settings determine the source of the frequency
Reference 1 or 2 (b1-01, b1-02 or b1-15, b1-16)
Closed: LOCAL, Frequency reference and Run command are input from
the digital operator
Closed: No converter output
Open: No converter output
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
Select this setting when using the terminal in a pass-through mode.
Closed: Resets faults if the cause is cleared and the Run command is
removed.
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in
conjunction with the timer function output (H2-
Values
Default: 4B
Min.: 1
Max.: 67
Default: 4C
Min.: 1
Max.: 67
Default: 24H
Min.: 0
Max.: 67
Default: 14H
Min.: 0
Max.: 67
Default: F
Min.: 0
Max.: 67
Default: F
Min.: 0
Max.: 67
Default: F
Min.: 0
Max.: 67
Default: 8H
Min.: 0
Max.: 67
= 12).