3.1.13 Joint calibration
After replacement of joint it is required to calibrate the new joint in order to find the correct zero position
of joint.
Instruction for calibrating a joint
Jog robot to HOME position
Illustration shows the HOME position, which is defined as zero position of all joints.
Drag a finger from left to right across the UNIVERSAL-sign on main screen of PolyScope.