1MRK 505 277-UUS C
Section 18
18.1
Technical Manual
IED and functionality tests
Electromagnetic compatibility tests
Table 399:
Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
•
Common mode
•
Differential mode
Electrostatic discharge test
•
Contact discharge
•
Air discharge
Radio frequency interference
tests
•
Conducted, common mode
•
Radiated, amplitude-
modulated
Fast transient disturbance tests
•
Communication ports
•
Other ports
Surge immunity test
•
Communication
•
Other ports
Power frequency (50 Hz)
magnetic field
Table continues on next page
IED and functionality tests
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
20 V/m (rms), f=80...1000 MHz
and f=1.4...2.7 GHz
4 kV
4 kV
1 kV line-to-ground
2 kV line-to-ground, 1 kV line-to-
line
Section 18
Reference
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2002
IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
IEC 61000-4-6 , level 3
IEC 60255-22-6
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2002
IEC 61000-4-5, level 3/2
IEC 60255-22-5
IEC 61000-4-8, level 5
455