Section 18 Ied And Functionality Tests - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
Section 18
18.1
Technical Manual
IED and functionality tests
Electromagnetic compatibility tests
Table 399:
Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
Common mode
Differential mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency interference
tests
Conducted, common mode
Radiated, amplitude-
modulated
Fast transient disturbance tests
Communication ports
Other ports
Surge immunity test
Communication
Other ports
Power frequency (50 Hz)
magnetic field
Table continues on next page
IED and functionality tests
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
20 V/m (rms), f=80...1000 MHz
and f=1.4...2.7 GHz
4 kV
4 kV
1 kV line-to-ground
2 kV line-to-ground, 1 kV line-to-
line
Section 18
Reference
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2002
IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
IEC 61000-4-6 , level 3
IEC 60255-22-6
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2002
IEC 61000-4-5, level 3/2
IEC 60255-22-5
IEC 61000-4-8, level 5
455