Signals - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 8
Voltage protection
8.1.4
8.1.5
Table 67:
UV2PTUV (27) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationStep1
Disabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
OpMode1
1 out of 3
2 out of 3
3 out of 3
Pickup1
1 - 100
t1
0.00 - 6000.00
Table continues on next page
124

Signals

Table 65:
UV2PTUV (27) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK1
BOOLEAN
BLK2
BOOLEAN
Table 66:
UV2PTUV (27) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST1_A
BOOLEAN
PU_ST1_B
BOOLEAN
PU_ST1_C
BOOLEAN
PU_ST2
BOOLEAN
Settings
Unit
Step
-
-
-
-
-
-
-
-
%VB
1
s
0.01
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
0
Block of step 1
0
Block of step 2
Description
Common trip signal
Trip signal from step 1
Trip signal from step 2
General pickup signal
Start signal from step 1
Pick up signal from step 1 phase A
Pick up signal from step 1 phase B
Pick up signal from step 1 phase C
Start signal from step 2
Default
Description
Disabled
Disable/Enable Operation
Enabled
Enable execution of step 1
Definite time
Selection of time delay curve type for step 1
1 out of 3
Number of phases required to operate (1 of 3,
2 of 3, 3 of 3) from step 1
70
Voltage start value (DT & IDMT) in % of
VBase for step 1
5.00
Definite time delay of step 1
1MRK 505 277-UUS C
Technical Manual