1MRK 505 277-UUS C
9.2.3
9.2.4
9.2.5
Table 91:
TCSSCBR Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tDelay
0.020 - 300.000
9.2.6
Technical Manual

Function block

GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 62:
Function block
Signals
Table 89:
TCSSCBR Input signals
Name
Type
TCS_STATE
BOOLEAN
BLOCK
BOOLEAN
Table 90:
TCSSCBR Output signals
Name
Type
ALARM
BOOLEAN
Settings
Unit
Step
-
-
s
0.001
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are Enable and Disable.
The operation of trip circuit supervision can be described by using a module diagram.
All the modules in the diagram are explained in the next sections.
Secondary system supervision
Default
Description
0
Trip circuit fail indication from I/O-card
0
Block of function
Description
Trip circuit fault indication
Default
Description
Enabled
Operation Disabled/Enabled
3.000
Operate time delay
Section 9
157