Insulation Tests; Mechanical Tests - ABB REM 610 Product Manual

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

Motor Protection Relay
Technical data (cont´d)
Table 13: Electromagnetic compatibility tests
Table 14: Standard tests
Table 15: Data communication
All manuals and user guides at all-guides.com
Voltage dips and short interruptions
Electromagnetic emission tests
Conducted, RF-emission (Mains terminal)
Radiated RF-emission
CE approval

Insulation tests

Dielectric tests
Test voltage
Impulse voltage test
Test voltage
Insulation resistance measurements
Isolation resistance

Mechanical tests

Vibration tests (sinusoidal)
Shock and bump test
Rear interface, connector X5.3 or X5.5
Fibre-optic or RS-485 connection
SPA bus, IEC 60870-5-103 or Modbus protocol
9.6 or 4.8 kbps (additionally 2.4, 1.2 or 0.3 kbps for Modbus)
Front interface
Optical connection (infrared): wirelessly or via the front communication cable (1MRS050698)
SPA bus protocol
9.6 or 4.8 kbps (9.6 kbps with front communication cable)
REM 610
1MRS 755121
According to the IEC 61000-4-11
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
According to the EN 55011
EN 55011, class A, IEC 60255-25
EN 55011, class A, IEC 60255-25
Complies with the EMC directive
89/336/EEC and the LV directive
73/23/EEC
According to the IEC 60255-5
2 kV, 50 Hz, 1 min
According to the IEC 60255-5
5 kV, unipolar impulses, waveform
1.2/50 µs, source energy 0.5 J
According to the IEC 60255-5
>100 MΩ, 500 V dc
According to the IEC 60255-21-1, class I
According to the IEC 60255-21-2, class I
9