Blocking - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
8.3.7.3
8.3.7.4
Technical Manual
TD
480
t
=
+
V Vpickup
>
32
0 5
.
Vpickup
>
ANSIEQUATION2288 V2 EN
The details of the different inverse time characteristics are shown in section
time
characteristics".
TRIP signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter t1 and t2 for
definite time mode (DT) and by some special voltage level dependent time curves for
the inverse time mode (TOV).
If the PICKUP condition, with respect to the measured voltage ceases during the delay
time, the corresponding PICKUP output is reset.

Blocking

It is possible to block two step residual overvoltage protection (ROV2PTOV, 59N)
partially or completely, by binary input signals where:
BLOCK:
BLK1:
BLK2:
Design
The voltage measuring elements continuously measure the residual voltage. Recursive
Fourier filters filter the input voltage signal. The single input voltage is compared to
the set value, and is also used for the inverse time characteristic integration. The design
of Two step residual overvoltage protection (ROV2PTOV, 59N) is schematically
described in
Figure
56.
0 035
.
blocks all outputs
blocks all pickupand trip outputs related to step 1
blocks all pickup and trip inputs related to step 2
Section 8
Voltage protection
(Equation 36)
"Inverse
141

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents