Monitored Data - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 9
Secondary system supervision
9.1.6
9.1.7
9.1.7.1
148

Monitored data

Table 87:
SDDRFUF Monitored data
Name
Type
3I0
REAL
3I2
REAL
3V0
REAL
3V2
REAL
Operation principle
Zero and negative sequence detection
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates: (see figure 58)
the zero-sequence voltage 3V
the zero-sequence current 3I
the negative sequence current 3I
the negative sequence voltage 3V
The measured signals are compared with their respective set values 3V0PU and 3I0PU,
3V2PU and 3I2PU.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value 3V0PU and the measured zero-sequence
current is below the set value 3I0PU.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value 3V2PU and the measured negative
sequence current is below the set value 3I2PU.
A drop off delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the two
line ends.
Values (Range)
Unit
-
A
-
A
-
kV
-
kV
0
0
2
2
1MRK 505 277-UUS C
Description
Magnitude of zero sequence
current
Magnitude of negative
sequence current
Magnitude of zero sequence
voltage
Magnitude of negative
sequence voltage
Technical Manual