Single Point Generic Control 8 Signals Spc8Ggio - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 10
Control
10.5
10.5.1
10.5.2
10.5.3
10.5.4
174

Single point generic control 8 signals SPC8GGIO

Identification
Function description
Single point generic control 8 signals
Functionality
The Single point generic control 8 signals (SPC8GGIO) function block is a collection
of 8 single point commands, designed to bring in commands from REMOTE (SCADA)
to those parts of the logic configuration that do not need extensive command receiving
functionality (for example, SCSWI). In this way, simple commands can be sent
directly to the IED outputs, without confirmation. Confirmation (status) of the result of
the commands is supposed to be achieved by other means, such as binary inputs and
SPGGIO function blocks. The commands can be pulsed or steady.
Function block
SPC8GGIO
BLOCK
^OUT1
PSTO
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
IEC09000086_1_en.vsd
IEC09000086 V1 EN
Figure 70:
SPC8GGIO function block
Signals
Table 111:
SPC8GGIO Input signals
Name
Type
BLOCK
BOOLEAN
PSTO
INTEGER
IEC 61850
IEC 60617
identification
identification
SPC8GGIO
Default
Description
0
Block of function
2
Operator place selection
1MRK 505 277-UUS C
ANSI/IEEE C37.2
device number
-
-
Technical Manual