Section 7
Current protection
7.3.4
7.3.5
Table 42:
TRPTTR (49) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IRef
10.0 - 1000.0
IBase1
30.0 - 250.0
IBase2
30.0 - 250.0
Tau1
1.0 - 500.0
Tau2
1.0 - 500.0
IHighTau1
30.0 - 250.0
Table continues on next page
102

Signals

TRPTTR is not provided with external temperature sensor in first
release of 650 series. The only input that influences the temperature
measurement is the binary input COOLING.
Table 40:
TRPTTR (49) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
COOLING
BOOLEAN
RESET
BOOLEAN
Table 41:
TRPTTR (49) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
ALARM1
BOOLEAN
ALARM2
BOOLEAN
LOCKOUT
BOOLEAN
WARNING
BOOLEAN
Settings
Unit
Step
-
-
%IB
1.0
%IB
1.0
%IB
1.0
Min
1.0
Min
1.0
%IB1
1.0
Default
Description
-
Three phase group signal for current input
0
Block of function
0
Cooling input changes IBase setting and time constant
0
Reset of function
Description
Trip Signal
Pickup signal
First level alarm signal
Second level alarm signal
Lockout signal
Trip within set warning time
Default
Description
Disabled
Disable/Enable Operation
100.0
Reference current in % of IBase
100.0
Base current IBase1 without cooling input in
% of IBase
100.0
Base current IBase2 with cooling input in %
of IBase
60.0
Time constant without cooling input
60.0
Time constant with cooling input
100.0
Current setting for rescaling TC1 by TC1-
IHIGH