Section 15
Basic IED functions
15.14.4
416
Name
Type
NonIPPackRecNorm
INTEGER
NonIPPackRecPoll
INTEGER
NonIPPackDisc
INTEGER

Operation principle

The Denial of service functions (DOSLAN1 and DOSFRNT) measures the IED load
from communication and, if necessary, limit it for not jeopardizing the IEDs control
and protection functionality due to high CPU load. The function has the following outputs:
LINKUP indicates the Ethernet link status
WARNING indicates that communication (frame rate) is higher than normal
ALARM indicates that the IED limits communication
Values (Range)
Unit
-
-
-
-
-
-
1MRK 505 277-UUS C
Description
Number of non IP packets
received in normal mode
Number of non IP packets
received in polled mode
Number of non IP packets
discarded