Settings - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 12
Monitoring
12.15.5
12.15.5.1
12.15.6
314

Settings

SSIMG Settings
Table 258:
Basic parameter group settings for the function SSIMG (GM01-)
Parameter
Range
Operation
Off
On
PressAlmLimit
0.00 - 25.00
PressLOLimit
0.00 - 25.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tPressureAlarm
0.000 - 60.000
tPressureLO
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetPressAlm
0.000 - 60.000
tResetPressLO
0.000 - 60.000
tResetTempLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
Operation principle
Insulation gas monitoring function SSIMG (63) is used to monitor gas pressure in the
circuit breaker. Two binary output signals are used from the circuit breaker to initiate
alarm signals, pressure below alarm level and pressure below lockout level. If the input
signal PRES_ALM is high, which indicate that the gas pressure in the circuit breaker is
below alarm level, the function initiates output signal PRES_ALM, pressure below
alarm level, after a set time delay and indicate that maintenance of the circuit breaker is
required. Similarly, if the input signal PRES_LO is high, which indicate gas pressure
in the circuit breaker is below lockout level, the function initiates output signal
PRES_LO, after a time delay. The two time delay settings, tPressureAlarm and
tPressureLO, are included in order not to initiate any alarm for short sudden changes in
Step
Default
Unit
-
Off
0.01
5.00
0.01
3.00
0.01
30.00
0.01
30.00
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
1MRK 505 277-UUS C
Description
-
Operation Off / On
-
Alarm setting for pressure
-
Pressure lockout setting
-
Temperature alarm level
setting of the medium
-
Temperature lockout
level of the medium
s
Time delay for pressure
alarm
s
Time delay for pressure
lockout indication
s
Time delay for
temperature alarm
s
Time delay for temperture
lockout
s
Reset time delay for
pressure alarm
s
Reset time delay for
pressure lockout
s
Reset time delay for
temperture lockout
s
Reset time delay for
temperture alarm
Technical Manual