Technical Data - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 9
Secondary system supervision
9.1.8
9.2
9.2.1
9.2.2
156
Figure 61:
Simplified logic diagram for fuse failure supervision function, Main logic

Technical data

Table 88:
SDDRFUF technical data
Function
Operate voltage, zero sequence
Operate current, zero sequence
Operate voltage, negative sequence
Operate current, negative sequence
Operate voltage change pickup
Operate current change pickup
Operate phase voltage
Operate phase current
Operate phase dead line voltage
Operate phase dead line current
Breaker close/trip circuit monitoring TCSSCBR
Identification
Function description
Breaker close/trip circuit monitoring
Functionality
The trip circuit monitoring function TCSSCBR is designed for supervision of control
circuits. A fault in a control circuit is detected by using a dedicated output contact that
contains the monitoring functionality.
The function picks up and trips when TCSSCBR detects a trip circuit failure. The trip
time characteristic for the function is of definite time (DT) type. The function trips
after a predefined operating time and resets when the fault disappears.
Range or value
(1-100)% of VBase
(1–100)% of IBase
(1–100)% of VBase
(1–100)% of IBase
(1–100)% of VBase
(1–100)% of IBase
(1-100)% of VBase
(1-100)% of IBase
(1-100)% of VBase
(1-100)% of IBase
IEC 61850
IEC 60617
identification
identification
TCSSCBR
-
1MRK 505 277-UUS C
Accuracy
± 1.0% of V
n
± 1.0% of I
n
± 0.5% of V
n
± 1.0% of I
n
± 5.0% of V
n
± 5.0% of I
n
± 0.5% of V
n
± 1.0% of I
n
± 0.5% of V
n
± 1.0% of I
n
ANSI/IEEE C37.2
device number
-
Technical Manual