Technical Data - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 12
Monitoring
12.14.9
12.15
12.15.1
12.15.2
12.15.3
312

Technical data

Table 255:
SPVNZBAT Technical data
Function
Lower limit for the battery
terminal voltage
Reset ratio, lower limit
Upper limit for the battery
terminal voltage
Reset ratio, upper limit
Timers
Insulation gas monitoring function SSIMG (63)
Identification
Function description
Insulation gas monitoring function
Functionality
Insulation gas monitoring function SSIMG (63) is used for monitoring the circuit
breaker condition. Binary information based on the gas pressure in the circuit breaker
is used as input signals to the function. In addition, the function generates alarms based
on received information.
Function block
SSIMG (63)
BLOCK
PRESSURE
BLK_ALM
PRES_ALM
PRESSURE
PRES_LO
TEMP
TEMP
PRES_ALM
TEMP_ALM
PRES_LO
TEMP_LO
SET_P_LO
SET_T_LO
RESET_LO
ANSI09000129-1-en.vsd
ANSI09000129 V1 EN
Figure 125:
SSIMG (63) function block
Range or value
(60-140) % of Vbat
<105 %
(60-140) % of Vbat
>95 %
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
SSIMG
-
1MRK 505 277-UUS C
Accuracy
± 1.0% of set battery voltage
-
± 1.0% of set battery voltage
-
± 0.5% ± 110 ms
ANSI/IEEE C37.2
device number
63
Technical Manual