Settings - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
7.6.5
Table 61:
DNSPTOC (46) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
RCADir
-180 - 180
ROADir
1 - 90
LowVolt_VM
0.0 - 5.0
Operation_OC1
Disabled
Enabled
PickupCurr_OC1
2.0 - 5000.0
MultPU_OC1
1.0 - 10.0
tDef_OC1
0.00 - 6000.00
Table continues on next page
Technical Manual
Name
Type
ENMLTOC1
BOOLEAN
BLKOC2
BOOLEAN
ENMLTOC2
BOOLEAN
Table 60:
DNSPTOC (46) Output signals
Name
Type
TRIP
BOOLEAN
TROC1
BOOLEAN
TROC2
BOOLEAN
BFI_3P
BOOLEAN
PU_OC1
BOOLEAN
PU_OC2
BOOLEAN
DIROC1
INTEGER
DIROC2
INTEGER
CURRENT
REAL
VOLTAGE
REAL
VIANGLE
REAL

Settings

Unit
Step
-
-
Deg
1
Deg
1
%VB
0.1
-
-
%IB
1.0
-
0.1
s
0.01
Default
Description
0
Enable signal for current multiplier - step1 (OC1)
0
Block of over current function OC2
0
Enable signal for current multiplier - step 2 (OC2)
Description
Common trip signal
Trip signal from step 1 (OC1)
Trip signal from step 2 (OC2)
General pickup signal
OC1_PICK UP
OC2_PICK UP
Directional mode of step 1(non-directional, forward,
reverse)
Directional mode of step 2 (non-directional, forward,
reverse)
Measured current value
Measured voltage value
Angle between voltage and current
Default
Description
Disabled
Disable/Enable Operation
-75
Relay characteristic angle
75
Relay operate angle
0.5
Voltage level in % of Vbase below which
ActLowVolt control takes over
Disabled
Operation DISABLE/ENABLE for step 1 (OC1)
120.0
Operate current level in % of IBase for step 1
(OC1)
2.0
Multiplier for current operate level for step 1
(OC1)
0.50
Independent (definite) time delay for step 1
(OC1)
Section 7
Current protection
119