ABB Relion 650 Series Product Manual

ABB Relion 650 Series Product Manual

Busbar protection version 1.1 ansi
Hide thumbs Also See for Relion 650 Series:

Advertisement

Quick Links

®
Relion
650 SERIES
Busbar protection REB650
Version 1.1 ANSI
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 650 Series

  • Page 1 ® Relion 650 SERIES Busbar protection REB650 Version 1.1 ANSI Product guide...
  • Page 2: Table Of Contents

    18. Ordering..................43 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Power Grids. ABB Power Grids assumes no responsibility for any errors that may appear in this document.
  • Page 3: Series Overview

    • Minimized parameter settings based on default values and ABB's new global base value concept. You only need • Complete busbar protection for two busbar sections to set those parameters specific to your own (zone 1 and 2), with the possibility for check zone (A03A) application, such as the line data.
  • Page 4 ANSI IEC61850 IEC60870-5-103 Feeder Bays Feeder Bays ANSI11000145_1_en.vsd ANSI11000145 V1 EN-US Figure 1. A typical busbar protection for two busbar sections with the possibility of a check zone ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 5: Available Functions

    52PD Pole discordance protection DNSPTOC Negative sequence based overcurrent function Voltage protection UV2PTUV Two step undervoltage protection OV2PTOV Two step overvoltage protection ROV2PTOV Two step residual overvoltage protection ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 6 TIMERSET Configurable logic blocks, timer function block Configurable logic blocks, AND gate SRMEMORY Configurable logic blocks, set-reset memory flip-flop gate RSMEMORY Configurable logic blocks, reset-set memory flip-flop gate ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 7 Function status auto-recloser for IEC60870-5-103 I103EF Function status earth-fault for IEC60870-5-103 I103FLTPROT Function status fault protection for IEC60870-5-103 I103IED IED status for IEC60870-5-103 I103SUPERV Supervison status for IEC60870-5-103 ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 8 GOOSEINTRCV GOOSE function block to receive an integer value GOOSEMVRCV GOOSE function block to receive a mesurand value GOOSESPRCV GOOSE function block to receive a single point value ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 9: Differential Protection

    CTs, a series resistor, and a voltage M12846-3 v9 The four step phase overcurrent protection function dependent resistor which are mounted externally OC4PTOC (51/67) has independent inverse time delay connected to the IED. ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 10 Breaker failure protection CCRBRF (50BF) M11550-6 v9 Breaker failure protection (CCRBRF, 50BF) ensures fast back-up tripping of surrounding breakers in case the protected breaker fails to open. CCRBRF (50BF) can be ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 11: Voltage Protection

    (DT) type. The function trips be set as inverse or definite time delayed. Step 2 is always after a predefined operating time and resets when the definite time delayed. fault disappears. ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 12: Control

    The timer has a those parts of the logic configuration that do not need settable time delay. extensive command receiving functionality (for example, ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 13: Monitoring

    Substation automation system about: Continuous event-logging is useful for monitoring the system from an overview perspective and is a complement to specific disturbance recorder functions. ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 14 IED. to definite time characteristics. The trip value recorder information is an integrated part of the disturbance record (Comtrade file). ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 15: Metering

    Values can be read or generated as pulses. ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 16: Basic Ied Functions

    (GOOSE) between highly adaptable IED that can cope with a variety of the IEDs, is only enabled by the IEC 61850-8-1 system scenarios. communication protocol. ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 17: Hardware Description

    5 ms. Table 1. Supported communication interface and protocol alternatives Interfaces/ Ethernet ST connector Protocols 100BASE-FX LC IEC 61850-8-1 ● DNP3 ● IEC 60870-5-103 ● ● = Supported ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 18 Figure 4. Flush mounted IED 224 mm + 12 mm with ring-lug connector 25.5 mm 482.6 mm (19") 222 mm 13 mm 27 mm 265.9 mm (6U) 13 mm ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 19: Connection Diagrams

    13 mm 268.9 mm GUID-5C185EAC-13D0-40BD-8511-58CA53EFF7DE V1 EN-US Figure 8. Main unit and detached LHMI display 25.5 mm 258.6 mm 220 mm 265.9 mm 13 mm 224 mm 265.9 mm ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 20: Technical Data

    100 V AC/ 110 V AC/ 115 V AC/ 120 V AC Voltage withstand: • Continuous 420 V rms • For 10 s 450 V rms Burden at rated voltage <0.05 VA Residual current Phase currents or residual current ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 21 10 A Make and carry 0.5 s 30 A ≤0.5 A/≤0.1 A/≤0.04 A Breaking capacity when the control-circuit time constant L/R<40 ms, at V< 48/110/220 V DC GUID-F773051A-F50F-4B12-8CB3-88936A687FDC v4 ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 22 Table 10. X4/IRIG-B interface Type Protocol Cable Screw terminal, pin row header IRIG-B Shielded twisted pair cable Recommended: CAT 5, Belden RS-485 (9841- 9844) or Alpha Wire (Alpha 6222-6230) ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 23 96 h at +85ºC Damp heat tests steady state 240 h at +40ºC IEC 60068-2-78 humidity 93% cyclic 6 cycles at +25 to +55ºC IEC 60068-2-30 humidity 93...95% ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 24 150 V rms Voltage dips and short interruptions Dips: IEC 60255-11 40%/200 ms IEC 61000-4-11 70%/500 ms Interruptions: 0-50 ms: No restart 0...∞ s : Correct behaviour at power down ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 25 Class 1 Shock response test IEC 60255-21-2 Class 1 Shock withstand test IEC 60255-21-2 Class 1 Bump test IEC 60255-21-2 Class 1 Seismic test IEC 60255-21-3 Class 2 ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 26 Reference LV directive 2006/95/EC Standard EN 60255-27 (2005) EMC compliance GUID-9B1F0C9F-664E-41C8-ADA3-4376E096A9C9 v4 Table 20. EMC compliance Description Reference EMC directive 2004/108/EC Standard EN 50263 (2000) EN 60255-26 (2007) ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 27 15 ms typically at 0 to 10 x V Reset time 90 ms typically at 10 to 0 x V Critical impulse time 2 ms typically at 0 to 10 x V ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 28 25 ms typically at 2 to 0 x I funciton Critical impulse time 10 ms typically at 0 to 2 x I Impulse margin time 15 ms typically ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 29 Operate time, directional 30 ms typically at 0,5 to 2 x I pickup function Reset time, directional pickup 30 ms typically at 2 to 0,5 x I function ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 30 Function Range or value Accuracy Operate value, current (0-100) % ± 1.0% of I asymmetry level Reset ratio >95% Time delay (0.000-60.000) s ± 0.5% ± 25 ms ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 31 Reset time, pickup function 40 ms typically at 0.5 to 2 x V Critical impulse time 10 ms typically at 2 to 0 x V Impulse margin time 15 ms typically ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 32 Reset time, pickup function 40 ms typically at 2 to 0 x V Critical impulse time 10 ms typically at 0 to 2 x V Impulse margin time 15 ms typically ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 33 ± 1.0% of I GUID-CF26761C-55B8-41EF-B140-651F7F116003 v2 Table 32. Breaker close/trip circuit monitoring TCSSCBR Function Range or value Accuracy Operate time delay (0.020 - 300.000) s ± 0,5% ± 110 ms ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 34 Accuracy 5 ms 20 ms 100 ms INVERTER SRMEMORY RSMEMORY GATE PULSETIMER (0.000–90000.000) s ± 0.5% ± 25 ms TIMERSET (0.000–90000.000) s ± 0.5% ± 25 ms LOOPDELAY ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 35 Accuracy valid for 50 Hz. At 60 Hz the accuracy is <0.04. M13416-1 v4 Table 36. Event counter CNTGGIO Function Range or value Accuracy Counter value 0-10000 Max. count up speed 10 pulses/s ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 36 Accuracy Depending on time synchronizing M13765-1 v4 Table 39. Indications DRPRDRE Function Value Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 37 Upper limit for the battery terminal voltage (60-140) % of Vbat ± 1.0% of set battery voltage Reset ratio, upper limit >95 % Timers (0.000-60.000) s ± 0.5% ± 110 ms ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 38 Table 48. Function for energy calculation and demand handling ETPMMTR Function Range or value Accuracy Energy metering MWh Export/Import, MVArh Input from MMXU. No extra error at steady load Export/Import ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 39 ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0 ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0 ANSI Long Time Inverse td=(0.05-999) in steps of 0.01 A=0.086, B=0.185, P=0.02 ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 40 = (0.05-999) in steps of 0.01 IEC 60255-151, class 5 + characteristic 40 ms æ ö ç × ÷ 1.35 è ø EQUATION1657 V1 EN-US I = I measured ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 41 = (0.05-1.10) in steps of 0.01 unless otherwise stated × 0.055 æ ö VPickup V × ç ÷ è ø VPickup EQUATION1659 V1 EN-US V = V measured ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 42 VPickup EQUATION1662 V1 EN-US Type C curve: td = (0.05-1.10) in steps of 0.01 × æ ö VPickup ç × ÷ 0.035 è ø VPickup EQUATION1663 V1 EN-US ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 43: Ordering

    Selection for position #4. Additional HMI language English US Selection for position #4. Casing Notes and Rules Rack casing, 6 U 1/2 x 19" Selection for position #5. ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 44 Slot position: Transformer module, 6I + 4U, 1/5A, 100/220V Included as basic Slot position: Analog input module, 6I + 4U, 1/5A, 100/220V Included as basic Selection for position #9. ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 45 Quantity : SEMOD131414-4 v2 LED Label special paper A4, 1 pc 1MRK 002 038-CA Quantity : LED Label special paper Letter, 1 pc 1MRK 002 038-DA Quantity : ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 46 Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name: Voltage level: ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 47 Communication protocol manual, IEC 60870-5-103 1MRK 511 243-UUS Point list manual, DNP3 1MRK 511 244-UUS Engineering manual 1MRK 511 245-UUS Operation manual 1MRK 500 093-UUS Installation manual 1MRK 514 014-UUS ABB Power Grids © Copyright 2011 ABB Power Grids. All rights reserved...
  • Page 49 ABB Power Grids Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Scan this QR code to visit our website Phone +46 (0) 10 738 00 00 www.abb.com/protection-control © Copyright 2011 ABB Power Grids. All rights reserved.