Section 14
Station communication
14.8
14.8.1
14.8.2
14.8.3
14.8.4
368
GOOSE function block to receive a single point value
GOOSESPRCV
Identification
Function description
GOOSE function block to receive a
single point value
Functionality
GOOSESPRCV is used to receive a single point value using IEC61850 protocol via
GOOSE.
Function block
GOOSESPRCV
BLOCK
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
IEC10000248 V1 EN
Figure 156:
GOOSESPRCV function block
Signals
Table 314:
GOOSESPRCV Input signals
Name
Type
BLOCK
BOOLEAN
Table 315:
GOOSESPRCV Output signals
Name
Type
SPOUT
BOOLEAN
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN
IEC 61850
IEC 60617
identification
identification
GOOSESPRCV
-
Default
Description
0
Block of function
Description
Single point output
Data valid for single point output
Communication valid for single point output
Test output