Signals - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
10.8.3
10.8.4
Table 122:
I103IEDCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
10.9
10.9.1
Technical Manual

Signals

Table 120:
I103IEDCMD Input signals
Name
Type
BLOCK
BOOLEAN
Table 121:
I103IEDCMD Output signals
Name
Type
19-LEDRS
BOOLEAN
23-GRP1
BOOLEAN
24-GRP2
BOOLEAN
25-GRP3
BOOLEAN
26-GRP4
BOOLEAN
Settings
Unit
Step
-
1
Function commands user defined for IEC
60870-5-103 I103USRCMD
Functionality
I103USRCMD is a command block in control direction with user defined output
signals. These function blocks include the FunctionType parameter for each block in
the private range, and the Information number parameter for each output signal.
Default
Description
0
Block of commands
Description
Information number 19, reset LEDs
Information number 23, activate setting group 1
Information number 24, activate setting group 2
Information number 25, activate setting group 3
Information number 26, activate setting group 4
Default
Description
255
Function type (1-255)
Section 10
Control
181

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents