Signal Outputs - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
17.5
17.6
Technical Manual

Signal outputs

Table 385:
Signal output and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
Power outputs
Table 386:
Power output relays without TCM function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
Table 387:
Power output relays with TCM function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
Control voltage range
Current drain through the monitoring circuit
Minimum voltage over the TCS contact
Technical data
Value
250 V AC/DC
5 A
10 A
30 A
≤0.5 A/≤0.1 A/≤0.04 A
Value
250 V AC/DC
8 A
15 A
30 A
≤1 A/≤0.3 A/≤0.1 A
Value
250 V DC
8 A
15 A
30 A
≤1 A/≤0.3 A/≤0.1 A
20...250 V DC
~1.0 mA
20 V DC
Section 17
451

Hide quick links:

Advertisement