Section 7
Current protection
7.4.3
7.4.4
108
Current check with extremely short reset time is used as check criterion to achieve high
security against unnecessary operation.
Contact check criteria can be used where the fault current through the breaker is small.
Breaker failure protection, 3-phase activation and output (CCRBRF, 50BF) current
criteria can be fulfilled by one or two phase currents the residual current, or one phase
current plus residual current. When those currents exceed the user defined settings, the
function is triggered. These conditions increase the security of the back-up trip command.
CCRBRF (50BF) function can be programmed to give a three-phase re-trip of the
protected breaker to avoid unnecessary tripping of surrounding breakers.

Function block

CCRBRF (50BF)
I3P*
TRBU
BLOCK
TRRET
BFI_3P
52A_A
52A_B
52A_C
ANSI09000272-1-en.vsd
ANSI09000272 V1 EN
Figure 43:
CCRBRF (50BF) function block
Signals
Table 46:
CCRBRF (50BF) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BFI_3P
BOOLEAN
52a_A
BOOLEAN
52a_B
BOOLEAN
52a_C
BOOLEAN
Table 47:
CCRBRF (50BF) Output signals
Name
Type
TRBU
BOOLEAN
TRRET
BOOLEAN
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Three phase breaker failure initiation
1
Circuit breaker closed in phase A
1
Circuit breaker closed in phase B
1
Circuit breaker closed in phase C
Description
Back-up trip by breaker failure protection function
Retrip by breaker failure protection function
1MRK 505 277-UUS C
Technical Manual