Settings - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 14
Station communication
14.9.2
Table 317:
OPTICAL103 Non group settings (basic)
Name
Values (Range)
SlaveAddress
1 - 31
BaudRate
9600 Bd
19200 Bd
RevPolarity
Disabled
Enabled
CycMeasRepTime
1.0 - 1800.0
MasterTimeDomain
UTC
Local
Local with DST
TimeSyncMode
IEDTime
LinMastTime
IEDTimeSkew
EvalTimeAccuracy
Disabled
5ms
10ms
20ms
40ms
EventRepMode
SeqOfEvent
HiPriSpont
Table 318:
RS485103 Non group settings (basic)
Name
Values (Range)
SlaveAddress
1 - 31
BaudRate
9600 Bd
19200 Bd
CycMeasRepTime
1.0 - 1800.0
Table continues on next page
370
IEC 60870-5-103 protocol can be configured to use either the optical serial or RS485
serial communication interface on the COM05 communication module. The functions
Operation selection for optical serial (OPTICALPROT) and Operation selection for
RS485 (RS485PROT) are used to select the communication interface.
See the Engineering manual for IEC103 60870-5-103 engineering
procedures in PCM600.
The functions IEC60870-5-103 Optical serial communication (OPTICAL103) and
IEC60870-5-103 serial communication for RS485 (RS485103) are used to configure
the communication parameters for either the optical serial or RS485 serial
communication interfaces.

Settings

Unit
Step
-
1
-
-
-
-
s
0.1
-
-
-
-
-
-
-
-
Unit
Step
-
1
-
-
s
0.1
Default
Description
1
Slave address
9600 Bd
Baudrate on serial line
Enabled
Invert polarity
5.0
Cyclic reporting time of measurments
UTC
Master time domain
IEDTime
Time synchronization mode
5ms
Evaluate time accuracy for invalid time
SeqOfEvent
Event reporting mode
Default
Description
1
Slave address
9600 Bd
Baudrate on serial line
5.0
Cyclic reporting time of measurments
1MRK 505 277-UUS C
Technical Manual