Function Block - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
7.5.3
7.5.4
7.5.5
Table 55:
CCRPLD (52PD) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tTrip
0.000 - 60.000
ContactSel
Disabled
PD signal from CB
Table continues on next page
Technical Manual

Function block

CCRPLD (52PD)
I3P*
TRIP
BLOCK
PICKUP
CLOSECMD
OPENCMD
EXTPDIND
ANSI08000041-1-en.vsd
ANSI08000041 V1 EN
Figure 46:
CCRPLD (52PD) function block
Signals
Table 53:
CCRPLD (52PD) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
CLOSECMD
BOOLEAN
OPENCMD
BOOLEAN
EXTPDIND
BOOLEAN
Table 54:
CCRPLD (52PD) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
-
-
s
0.001
-
-
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Close command to CB
0
Open command to CB
0
Pole discrepancy signal from CB logic
Description
Trip signal to CB
Trip condition TRUE, waiting for time delay
Default
Description
Disabled
Disable/Enable Operation
0.300
Time delay between trip condition and trip
signal
Disabled
Contact function selection
Section 7
Current protection
113