Insulation Tests - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
18.2
18.3
18.4
Technical Manual

Insulation tests

Table 400:
Insulation tests
Description
Dielectric tests:
Test voltage
Impulse voltage test:
Test voltage
Insulation resistance
measurements
Isolation resistance
Protective bonding resistance
Resistance
Mechanical tests
Table 401:
Mechanical tests
Description
Vibration response tests
(sinusoidal)
Vibration endurance test
Shock response test
Shock withstand test
Bump test
Seismic test
Product safety
IED and functionality tests
Type test value
2 kV, 50 Hz, 1 min
1 kV, 50 Hz, 1 min,
communication
5 kV, unipolar impulses,
waveform 1.2/50 μs, source
energy 0.5 J
1 kV, unipolar impulses,
waveform 1.2/50 μs, source
energy 0.5 J, communication
>100 MΏ, 500 V DC
<0.1 Ώ (60 s)
Reference
IEC 60255-21-1
IEC60255-21-1
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-3
Section 18
Reference
IEC 60255-5
ANSI C37.90-2005
IEC 60255-5
ANSI C37.90-2005
IEC 60255-5
ANSI C37.90-2005
IEC 60255-27
Requirement
Class 2
Class 1
Class 1
Class 1
Class 1
Class 2
457