Protective Ground Connections - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
Section 16
16.1
Technical Manual
IED physical connections

Protective ground connections

The IED shall be grounded with a 6 Gauge flat copper cable.
The ground lead should be as short as possible, less than 59.06 inches
(1500 mm). Additional length is required for door mounting.
ANSI11000286 V2 EN
Figure 174:
The protective ground pin is located to the left of connector X101 on
the 3U full 19" case
Section 16
IED physical connections
417

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents