Two step overvoltage protection (OV2PTOV, 59) function can be used to detect open
line ends, normally then combined with a directional reactive over-power function to
supervise the system voltage. When triggered, the function will cause an alarm, switch
in reactors, or switch out capacitor banks.
OV2PTOV (59) has two voltage steps, where step 1 can be set as inverse or definite
time delayed. Step 2 is always definite time delayed.
OV2PTOV (59) has an extremely high reset ratio to allow settings close to system
service voltage.

Function block

OV2PTOV (59)
V3P*
TRIP
BLOCK
TRST1
BLK1
TRST2
BLK2
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
ANSI09000278-1-en.vsd
ANSI09000278 V1 EN
Figure 52:
OV2PTOV function block (59)
Signals
Table 71:
OV2PTOV (59) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK1
BOOLEAN
BLK2
BOOLEAN
Table 72:
OV2PTOV (59) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
PICKUP
BOOLEAN
Table continues on next page
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
0
Block of step 1
0
Block of step 2
Description
Common trip signal
Trip signal from step 1
Trip signal from step 2
General pickup signal