Section 14
Station communication
14.7
14.7.1
14.7.2
14.7.3
366
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a
cross to receive the integer values.
The implementation for IEC61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
GOOSE function block to receive a measurand value
GOOSEMVRCV
Identification
Function description
GOOSE function block to receive a
measurand value
Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
Function block
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-1-en.vsd
IEC10000251 V1 EN
Figure 155:
GOOSEMVRCV function block
IEC 61850
IEC 60617
identification
identification
GOOSEMVRCV
-
1MRK 505 277-UUS C
ANSI/IEEE C37.2
device number
-
Technical Manual