Monitored Data - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 12
Monitoring
Name
Values (Range)
DrepChNoV_A
1 - 30
DrepChNoV_B
1 - 30
DrepChNoV_C
1 - 30
12.13.6
12.13.7
302
Unit
Step
Ch
1
Ch
1
Ch
1

Monitored data

Table 247:
LMBRFLO Monitored data
Name
Type
FLT_REL
REAL
FLT_DIST
REAL
FLT_X
REAL
FLT_R
REAL
FLT_LOOP
INTEGER
Operation principle
The Fault locator (LMBRFLO) in the IED is an essential complement to other
monitoring functions, since it measures and indicates the distance to the fault with high
accuracy.
When calculating distance to fault, pre-fault and fault phasors of currents and voltages
are selected from the Trip value recorder data, thus the analog signals used by the fault
locator must be among those connected to the disturbance report function. The analog
configuration (channel selection) is performed using the parameter setting tool within
PCM600.
The calculation algorithm considers the effect of load currents, double-end infeed and
additional fault resistance.
Default
Description
5
Recorder Input number recording phase
voltage, VA
6
Recorder Input number recording phase
voltage, VB
7
Recorder Input number recording phase
voltage, VC
Values (Range)
Unit
-
-
-
-
-
Ohm
-
Ohm
0=---
-
1=L1-N
2=L2-N
3=L3-N
4=L1-L2
5=L2-L3
6=L3-L1
7=L1-L2-L3
1MRK 505 277-UUS C
Description
Distance to fault, relative
Distance to fault in line length
unit
Reactive distance to fault
Resistive distance to fault
Fault loop
Technical Manual