Monitored Data - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
Name
Values (Range)
Tau1High
5 - 2000
ILowTau1
30.0 - 250.0
Tau1Low
5 - 2000
IHighTau2
30.0 - 250.0
Tau2High
5 - 2000
ILowTau2
30.0 - 250.0
Tau2Low
5 - 2000
ITrip
50.0 - 250.0
Alarm1
50.0 - 99.0
Alarm2
50.0 - 99.0
LockoutReset
10.0 - 95.0
Warning
1.0 - 500.0
Table 43:
TRPTTR (49) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
7.3.6
Technical Manual
Unit
Step
%tC1
1
%IB1
1.0
%tC1
1
%IB2
1.0
%tC2
1
%IB2
1.0
%tC2
1
%IBx
1.0
%Itr
1.0
%Itr
1.0
%Itr
1.0
Min
0.1
Unit
Step
-
1

Monitored data

Table 44:
TRPTTR (49) Monitored data
Name
Type
TTRIP
REAL
TTRIPCAL
INTEGER
TRESCAL
INTEGER
TRESLO
REAL
HEATCONT
REAL
I-MEASUR
REAL
Default
Description
100
Multiplier to TC1 when current is >IHIGH-TC1
100.0
Current setting for rescaling TC1 by TC1-ILOW
100
Multiplier to TC1 when current is <ILOW-TC1
100.0
Current setting for rescaling TC2 by TC2-
IHIGH
100
Multiplier to TC2 when current is >TC2-IHIGH
100.0
Current setting for rescaling TC2 by TC2-ILOW
100
Multiplier to TC2 when current is <ILOW-TC2
110.0
Steady state operate current level
80.0
First alarm level
90.0
Second alarm level
60.0
Lockout reset level
30.0
Time setting, below which warning would be
set
Default
Description
1
Selection of one of the Global Base Value
groups
Values (Range)
Unit
-
-
-
-
-
-
-
-
-
%
-
%
Section 7
Current protection
Description
Estimated time to trip (in min)
Calculated time status to trip:
not active/long time/active
Calculated time status to
reset: not active/long time/
active
Estimated time to reset of the
function (in min)
Percentage of the heat
content of the transformer
Current measured by the
function in % of the rated
current
103