Section 6
Differential protection
6.1.4
6.1.5
Table 24:
HZPDIF (87) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
AlarmPickup
2 - 500
tAlarm
0.000 - 60.000
TripPickup
5 - 900
R series
10 - 20000
6.1.6
6.1.7
70

Signals

Table 22:
HZPDIF (87) Input signals
Name
Type
ISI
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
Table 23:
HZPDIF (87) Output signals
Name
Type
TRIP
BOOLEAN
ALARM
BOOLEAN
MEASVOLT
REAL
Settings
Unit
Step
-
-
V
1
s
0.001
V
1
ohm
1
Monitored data
Table 25:
HZPDIF (87) Monitored data
Name
Type
MEASVOLT
REAL
Operation principle
The 1Ph High impedance differential protection (HZPDIF, 87) function is based on
one current input with external stabilizing resistor and voltage dependent resistor.
Default
Description
-
Group signal for current input
0
Block of function
0
Block of trip
Description
Trip signal
Alarm signal
Measured RMS voltage on CT secondary side
Default
Description
Disabled
Disable/Enable Operation
10
Alarm voltage level on CT secondary
5.000
Time delay to activate alarm
100
Pickup voltage level in volts on CT secondary
side
1800
Value of series resistor in Ohms
Values (Range)
Unit
-
kV
1MRK 505 277-UUS C
Description
Measured RMS voltage on
CT secondary side
Technical Manual