Blocking - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
8.2.7.3
8.2.7.4
Technical Manual

Blocking

It is possible to block two step overvoltage protection (OV2PTOV ,59) partially or
completely, by binary input signals where:
BLOCK:
BLK1:
BLK2:
Design
The voltage measuring elements continuously measure the three phase-to-ground
voltages or the three phase-to-phase voltages. Recursive Fourier filters filter the input
voltage signals. The phase voltages are individually compared to the set value, and the
highest voltage is used for the inverse time characteristic integration. A special logic is
included to achieve the 1 out of 3, 2 out of 3 or 3 out of 3 criteria to fulfill the PICKUP
condition. The design of Two step overvoltage protection (OV2PTOV, 59) is
schematically described in
blocks all outputs
blocks all pickup and trip outputs related to step 1
blocks all pickup and trip outputs related to step 2
Figure
54.
Section 8
Voltage protection
135