2.2 SPECIFICATIONS

2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
NOTE
2
interfacing with other IEDs or power system devices via communications or different output contacts.
TRIP BUS (TRIP WITHOUT FLEXLOGIC™)
Number of elements:
Number of inputs:
Operate time:
Time accuracy:
FLEXLOGIC™
Programming language: Reverse Polish Notation with graphical
Lines of code:
Internal variables:
Supported operations:
Inputs:
Number of timers:
Pickup delay:
Dropout delay:
FLEXCURVES™
Number:
Reset points:
Operate points:
Time delay:
FLEX STATES
Number:
Programmability:
FLEXELEMENTS™
Number of elements:
Operating signal:
Operating signal mode: signed or absolute value
Operating mode:
Comparator direction:
Pickup Level:
Hysteresis:
Delta dt:
Pickup & dropout delay: 0.000 to 65.535 s in steps of 0.001
2-8
6
16
<2 ms at 60 Hz
±3% or 10 ms, whichever is greater
visualization (keypad programmable)
512
64
NOT, XOR, OR (2 to 16 inputs), AND (2
to 16 inputs), NOR (2 to 16 inputs),
NAND (2 to 16 inputs), latch (reset-domi-
nant), edge detectors, timers
any logical variable, contact, or virtual
input
32
0 to 60000 (ms, sec., min.) in steps of 1
0 to 60000 (ms, sec., min.) in steps of 1
4 (A through D)
40 (0 through 1 of pickup)
80 (1 through 20 of pickup)
0 to 65535 ms in steps of 1
up to 256 logical variables grouped
under 16 Modbus addresses
any logical variable, contact, or virtual
input
8
any analog actual value, or two values in
differential mode
level, delta
over, under
–90.000 to 90.000 pu in steps of 0.001
0.1 to 50.0% in steps of 0.1
20 ms to 60 days
C30 Controller System
2 PRODUCT DESCRIPTION

2.2.1 PROTECTION ELEMENTS

2.2.2 USER-PROGRAMMABLE ELEMENTS

NON-VOLATILE LATCHES
Type:
set-dominant or reset-dominant
Number:
16 (individually programmed)
Output:
stored in non-volatile memory
Execution sequence:
as input prior to protection, control, and
FlexLogic™
USER-PROGRAMMABLE LEDs
Number:
48 plus trip and alarm
Programmability:
from any logical variable, contact, or vir-
tual input
Reset mode:
self-reset or latched
LED TEST
Initiation:
from any digital input or user-program-
mable condition
Number of tests:
3, interruptible at any time
Duration of full test:
approximately 3 minutes
Test sequence 1:
all LEDs on
Test sequence 2:
all LEDs off, one LED at a time on for 1 s
Test sequence 3:
all LEDs on, one LED at a time off for 1 s
USER-DEFINABLE DISPLAYS
Number of displays:
16
Lines of display:
2 × 20 alphanumeric characters
Parameters:
up to 5, any Modbus register addresses
Invoking and scrolling:
keypad, or any user-programmable con-
dition, including pushbuttons
CONTROL PUSHBUTTONS
Number of pushbuttons: 7
Operation:
drive FlexLogic™ operands
USER-PROGRAMMABLE PUSHBUTTONS (OPTIONAL)
Number of pushbuttons: 12 (standard faceplate);
16 (enhanced faceplate)
Mode:
self-reset, latched
Display message:
2 lines of 20 characters each
Drop-out timer:
0.00 to 60.00 s in steps of 0.05
Autoreset timer:
0.2 to 600.0 s in steps of 0.1
Hold timer:
0.0 to 10.0 s in steps of 0.1