Menus - GE C30 Instruction Manual

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

4 HUMAN INTERFACES
For the following discussion it is assumed the
setting is "Enabled" for each breaker.
1(2) PUSH BUTTON CONTROL
c) FACEPLATE (USER KEY) CONTROL
After the 30 minute interval during which command functions are permitted after a correct command password, the user
cannot open or close a breaker via the keypad. The following discussions begin from the not-permitted state.
d) CONTROL OF TWO BREAKERS
For the following example setup, the (Name) field represents the user-programmed variable name.
For this application (setup shown below), the relay is connected and programmed for both breaker 1 and breaker 2. The
USER 1 key performs the selection of which breaker is to be operated by the USER 2 and USER 3 keys. The USER 2 key
is used to manually close the breaker and the USER 3 key is used to manually open the breaker.
ENTER COMMAND
PASSWORD
Press USER 1
To Select Breaker
BKR1-(Name) SELECTED
USER 2=CLS/USER 3=OP
(1)
USER 2 OFF/ON
To Close BKR1-(Name)
(2)
USER 3 OFF/ON
To Open BKR1-(Name)
(3)
BKR2-(Name) SELECTED
USER 2=CLS/USER 3=OP
e) CONTROL OF ONE BREAKER
For this application the relay is connected and programmed for breaker 1 only. Operation for this application is identical to
that described above for two breakers.
a) NAVIGATION
Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily fol-
lowed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
Actual values.
Settings.
Commands.
Targets.
User displays (when enabled).
GE Multilin

SETTINGS
SYSTEM SETUP
This message appears when the USER 1, USER 2, or USER 3 key is pressed and a
is required; i.e. if
COMMAND PASSWORD
mands have been issued within the last 30 minutes.
This message appears if the correct password is entered or if none is required. This mes-
sage will be maintained for 30 seconds or until the USER 1 key is pressed again.
This message is displayed after the USER 1 key is pressed for the second time. Three
possible actions can be performed from this state within 30 seconds as per items (1), (2)
and (3) below:
If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is
pressed again within that time, a signal is created that can be programmed to operate an
output relay to close breaker 1.
If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is
pressed again within that time, a signal is created that can be programmed to operate an
output relay to open breaker 1.
If the USER 1 key is pressed at this step, this message appears showing that a different
breaker is selected. Three possible actions can be performed from this state as per (1),
(2) and (3). Repeatedly pressing the USER 1 key alternates between available breakers.
Pressing keys other than USER 1, 2 or 3 at any time aborts the breaker control function.
C30 Controller System
4.3 FACEPLATE INTERFACE

BREAKERS
BREAKER 1(2)
is enabled and no com-
COMMAND PASSWORD

BREAKER
4

4.3.7 MENUS

4-23

Advertisement

Table of Contents
loading

Table of Contents