GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

GE
Digital Energy
C30
Controller System
Instruction Manual
Product version: 7.3x
GE publication code: 1601-0088-AB1 (GEK-119612)
E83849
LISTED
IND.CONT. EQ.
52TL
1601-0088-AB1

Advertisement

Table of Contents
loading

Summary of Contents for GE C30

  • Page 1 Digital Energy Controller System Instruction Manual Product version: 7.3x GE publication code: 1601-0088-AB1 (GEK-119612) E83849 LISTED IND.CONT. EQ. 52TL 1601-0088-AB1...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3: Table Of Contents

    3.2.1 Horizontal units ........................3-2 3.2.2 Vertical units..........................3-3 3.2.3 Rear terminal layout ......................3-7 Wiring ......................... 3-9 3.3.1 Typical wiring ........................... 3-9 3.3.2 Dielectric strength........................3-10 3.3.3 Control power ........................3-10 3.3.4 Process bus modules......................3-11 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 4 3.7.3 Automatic discovery of UR devices................3-46 Connect to the C30..................3-46 3.8.1 Connect to the C30 in EnerVista ................... 3-46 3.8.2 Use Quick Connect via the front panel RS232 port ..........3-47 3.8.3 Use Quick Connect via a rear Ethernet port............3-48 Set up CyberSentry and change default password .........3-53...
  • Page 5 Contact outputs .........................5-151 5.8.4 Virtual outputs ........................5-154 5.8.5 Resetting..........................5-154 5.8.6 Direct inputs and outputs....................5-155 5.8.7 Teleprotection........................5-158 Transducer inputs/outputs ................5-160 5.9.1 DCmA inputs........................5-160 5.9.2 RTD inputs..........................5-161 5.9.3 DCmA outputs........................5-162 5.10 Testing......................5-164 5.10.1 Test mode function......................5-164 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 6 Targets menu ....................7-4 7.2.1 Target messages........................7-4 7.2.2 Relay self-tests.........................7-5 8 MAINTENANCE General maintenance ..................8-1 8.1.1 In-service maintenance.......................8-1 8.1.2 Out-of-service maintenance .....................8-1 8.1.3 Unscheduled maintenance (system interruption) ...........8-2 Back up and restore settings ................. 8-2 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 7 Clear files and data after uninstall ............. 8-12 A FLEXANALOG A.1 FlexAnalog items .....................A-1 OPERANDS B RADIUS SERVER B.1 RADIUS server configuration ................. B-1 CONFIGURATION C MISCELLANEOUS C.1 Warranty ......................C-1 C.2 Revision history ....................C-1 ABBREVIATIONS INDEX C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 8 TABLE OF CONTENTS viii C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 9: Introduction

    Ensure that the control power applied to the device, the AC current, and voltage input match the ratings specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 10: For Further Assistance

    Worldwide telephone: +1 905 927 7070 Europe/Middle East/Africa telephone: +34 94 485 88 54 North America toll-free: 1 800 547 8629 Fax: +1 905 927 5098 Worldwide e-mail: multilin.tech@ge.com Europe e-mail: multilin.tech.euro@ge.com Website: http://www.gedigitalenergy.com/multilin C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 11: Product Description

    This chapter outlines the product, order codes, and specifications. 2.1 Product description The C30 Controller System is part of the Universal Relay (UR) series of products. It is a microprocessor-based device designed for power substation control and monitoring. Diagnostic features include a sequence of records capable of storing 1024 time-tagged events. The internal clock used for time-tagging can be synchronized with an IRIG-B signal, using the Simple Network Time Protocol (SNTP) over the Ethernet port, or using the Precision Time Protocol (PTP).
  • Page 12: Security

    The C30 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear communications port.
  • Page 13 This means that the EnerVista software allows for access to functionality based on the user’s logged in role. Example: Observer cannot write any settings. The table lists user roles and their corresponding capabilities. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 14 |---------- Grouped Elements |---------- Control Elements |---------- Inputs / Outputs |--------------- Contact Inputs |--------------- Contact Input threshold |--------------- Virtual Inputs |--------------- Contact Outputs |--------------- Virtual Outputs |--------------- Resetting |--------------- Direct Inputs |--------------- Direct Outputs |--------------- Teleprotection C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 15: Order Codes

    The order code is on the product label and indicates the product options applicable. The C30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit. It consists of the following modules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay communications.
  • Page 16: Order Codes With Enhanced Ct/Vt Modules

    CT/VT modules or HardFiber process bus module). The process bus module provides an interface to HardFiber Bricks. 2.3.1 Order codes with enhanced CT/VT modules Table 2-3: C30 order codes for horizontal units - * * - F ** - H **...
  • Page 17 Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels Table 2-4: C30 order codes for reduced-size vertical units - * * - F ** - H ** - M **...
  • Page 18: Order Codes With Process Bus Modules

    G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 2.3.2 Order codes with process bus modules Table 2-5: C30 order codes for horizontal units with process bus - * * - F ** - H ** - M **...
  • Page 19 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 20 ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION Table 2-6: C30 order codes for reduced-size vertical units with process bus - * * - F ** - H ** - M ** - P/R Reduced Size Vertical Mount (see note regarding P/R slot below)
  • Page 21: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules apply to the C30 relay. The modules specified in the order codes for the C30 are available as replacement modules for the C30.
  • Page 22 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 2-12 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 23: Specifications

    FlexLogic USER-PROGRAMMABLE LEDs Number: 48 plus trip and alarm Programmability: from any logical variable, contact, or virtual input Reset mode: self-reset or latched LED TEST Initiation: from any contact input or user-programmable condition C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 2-13...
  • Page 24: Monitoring

    FlexLogic equation Data: AC input channels; element state; contact input state; contact output state Data storage: in non-volatile memory 2-14 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 25: Inputs

    0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10, 0 to 20, 4 to 20 (programmable) 379 ±10% Input impedance: Conversion range: –1 to + 20 mA DC Accuracy: ±0.2% of full scale Type: Passive C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 2-15...
  • Page 26: Power Supply

    88 V at 25 to 100 Hz Maximum AC voltage: 265 V at 25 to 100 Hz Voltage loss hold-up: 200 ms duration at maximum load ALL RANGES 2  Highest Nominal Voltage for 10 ms Volt withstand: 2-16 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 27: Outputs

    1 to 2.5 mA FORM-A CURRENT MONITOR Threshold current: approx. 80 to 100 mA FORM-C AND CRITICAL FAILURE RELAY Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous: C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 2-17...
  • Page 28 L/R = 20 ms 0.8 A L/R = 40 ms CONTROL POWER EXTERNAL OUTPUT (FOR DRY CONTACT INPUT) Capacity: 100 mA DC at 48 V DC Isolation: ±300 Vpk DIRECT OUTPUTS Output points: 2-18 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 29: Communication Protocols

    RJ45 SIMPLE NETWORK TIME PROTOCOL (SNTP) Clock synchronization error: <10 ms (typical) PRECISION TIME PROTOCOL (PTP) PTP IEEE Std 1588 2008 (version 2) Power Profile (PP) per IEEE Standard PC37.238TM2011 Slave-only ordinary clock Peer delay measurement mechanism C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 2-19...
  • Page 30: Inter-Relay Communications

    820 nm LED, Multimode –7.6 dBm 1300 nm LED, Multimode –11 dBm 1300 nm ELED, Single mode –14 dBm 1300 nm Laser, Single mode –14 dBm 1550 nm Laser, Single mode –14 dBm 2-20 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 31: Environmental

    –40 to 60°C; the LCD contrast can be impaired at temperatures less than –20°C HUMIDITY Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days) OTHER Altitude: 2000 m (maximum) Pollution degree: Overvoltage category: Ingress protection: IP20 front, IP10 back C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 2-21...
  • Page 32: Type Tests

    NKCR Safety IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over voltage cat II 2.4.10 Production tests THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. 2-22 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 33: Approvals

    Normally, cleaning is not required. When dust has accumulated on the faceplate display, wipe with a dry cloth. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 2-23...
  • Page 34 SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION 2-24 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 35: Installation

    For any issues, contact GE Digital Energy as outlined in the For Further Assistance section in chapter 1. Check that you have the latest copy of the C30 Instruction Manual and the UR Series Communications Guide, for the applicable firmware version, at http://gedigitalenergy.com/multilin/manuals/index.htm...
  • Page 36: Panel Cutouts

    This section does not apply to the HardFiber Brick; see its instruction manual. 3.2.1 Horizontal units The C30 is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 37: Vertical Units

    3.2.2 Vertical units The C30 is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 38 The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. Figure 3-4: Vertical dimensions (enhanced panel) C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 39 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-5: Vertical and mounting dimensions (standard panel) For details on side-mounting C30 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Digital Energy website. •...
  • Page 40 PANEL CUTOUTS CHAPTER 3: INSTALLATION For details on side-mounting C30 devices with the standard front panel, see the following figures. Figure 3-6: Vertical side-mounting installation (standard panel) C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 41: Rear Terminal Layout

    CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-7: Vertical side-mounting rear dimensions (standard panel) 3.2.3 Rear terminal layout Do not touch any rear terminals while the relay is energized. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 42 (nearest to CPU module), indicated by an arrow marker on the terminal block. The figure shows an example of rear terminal assignments. Figure 3-8: Example of modules in F and H slots C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 43: Wiring

    CHAPTER 3: INSTALLATION WIRING 3.3 Wiring 3.3.1 Typical wiring Figure 3-9: Typical wiring diagram (T module shown for CPU) C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 44: Dielectric Strength

    The power supply module can be ordered for two possible voltage ranges, and the C30 can be ordered with or without a redundant power supply module option. Each range has a dedicated input connection for proper operation. The ranges are as follows (see the Specifications section of chapter 2 for details): •...
  • Page 45: Process Bus Modules

    The terminal configuration for contact inputs is different for the two applications. The contact inputs are grouped with a common return. The C30 has two versions of grouping: four inputs per common return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
  • Page 46 See the Digital Elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be applied for breaker trip circuit integrity monitoring. Consider relay contacts unsafe to touch when the unit is energized. 3-12 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 47 ~6a, ~6c 2 Inputs Form-A ~7a, ~7c 2 Inputs Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-13...
  • Page 48 Not Used ~3a, ~3c 2 Inputs 2 Outputs Solid-State Solid-State ~4a, ~4c 2 Inputs 2 Outputs Not Used Not Used ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs 3-14 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 49 ~4D module ~4L module Terminal Output Terminal Output Terminal Output Terminal Output assignment assignment assignment assignment Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-15...
  • Page 50 WIRING CHAPTER 3: INSTALLATION Figure 3-12: Contact input and output module wiring (Sheet 1 of 2) 3-16 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 51 CONTACT IN COMMON DIGITAL I/O CONTACT IN SURGE CONTACT IN CONTACT IN CONTACT IN COMMON SURGE 842763A2.CDR For proper functionality, observe the polarity shown in the figures for all contact input and output connections. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-17...
  • Page 52 The contact inputs with auto-burnish create a high current impulse when the threshold is reached to burn off this oxidation layer as a maintenance to the contacts. Afterwards the contact input current is reduced to a steady-state current. The impulse has a five-second delay after a contact input changes state. 3-18 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 53: Transducer Inputs And Outputs

    Transducer input modules can receive input signals from external DCmA output transducers (DCmA In) or resistance temperature detectors (RTDs). Hardware and software are provided to receive signals from these external transducers and convert these signals into a digital format for use as required. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-19...
  • Page 54 (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. Where a tilde “~” symbol appears, substitute the slot position of the module. NOTE Figure 3-17: Transducer input/output module wiring The following figure show how to connect RTDs. 3-20 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 55: Rs232 Faceplate Port

    The baud rate for this port can be set, with a default of 19200 bps. Figure 3-19: RS232 faceplate port connection 3.3.8 CPU communication ports 3.3.8.1 Overview In addition to the faceplate RS232 port, there is a rear RS485 communication port. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-21...
  • Page 56 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the C30 COM terminal (#3); others function correctly only if the common wire is connected to the C30 COM terminal, but insulated from the shield.
  • Page 57: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the C30 operates an internal oscillator with 1 µs resolution and accuracy.
  • Page 58: Direct Input And Output Communications

    UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to UR4-Rx, and UR4-Tx to UR1-Rx. A maximum of 16 UR-series relays can be connected in a single ring. 3-24 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 59 1 to channel 2 on UR2, set the setting to “Enabled” on UR2. This DIRECT I/O CHANNEL CROSSOVER forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-25...
  • Page 60: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules. Figure 3-26: LED and ELED fiber modules 3.4.3 Fiber laser transmitters The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser modules. 3-26 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 61: Interface

    The following figure shows the 64K ITU G.703 co-directional interface configuration. The G.703 module is fixed at 64 kbps. The setting is not SETTINGS  PRODUCT SETUP  DIRECT I/O  DIRECT I/O DATA RATE applicable to this module. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-27...
  • Page 62 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is inserted fully. 3-28 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 63 (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). The switch settings for the internal and loop timing modes are shown. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-29...
  • Page 64 One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the interface. Figure 3-34: G.703 dual loopback mode DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR 3-30 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 65: Rs422 Interface

    1 are also paralleled to the terminal timing inputs of data module 2. By using this configuration, the timing for both data modules and both UR RS422 channels are derived from a single clock C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-31...
  • Page 66 831022A3.CDR Data module 1 provides timing to the C30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure because they vary by manufacturer.
  • Page 67: Rs422 And Fiber Interface

    G.703 and fiber interfaces. When using a laser interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-33...
  • Page 68: Ieee C37.94 Interface

    Connection — as per all fiber optic connections, a Tx to Rx connection is required The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports the IEEE C37.94 standard. The figure shows the concept. 3-34 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 69 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is inserted fully. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-35...
  • Page 70 Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the following figure. Figure 3-43: Status LEDs The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet 3-36 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 71: C37.94Sm Interface

    It also can be connected directly to any other UR-series relay with a C37.94SM module, as shown. The UR-series C37.94SM communication module has six switches that are used to set the clock configuration. The following figure shows the functions of these control switches. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-37...
  • Page 72 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is inserted fully. 3-38 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 73 Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the following figure. Figure 3-46: Status LEDs The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-39...
  • Page 74: Activate Relay

    RELAY SETTINGS: RELAY SETTINGS: NEW SETTING Not Programmed Programmed HAS BEEN STORED When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the "In Service" LED turns on. 3-40 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 75: Install Software

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the C30 rear communications port. The converter terminals (+, –, GND) are connected to the C30 communication module (+, –, COM) terminals. See the CPU Communication Ports section in chapter 3 for details.
  • Page 76: System Requirements

    Ethernet port of the same type as one of the UR CPU ports or a LAN connection to the UR • Internet access or a DVD drive The following qualified modems have been tested to be compatible with the C30 and the EnerVista software: • US Robotics external 56K FaxModem 5686 •...
  • Page 77: Configure The C30 For Software Access

    3.7 Configure the C30 for software access You connect remotely to the C30 through the rear RS485 or Ethernet port with a computer running the EnerVista UR Setup software. The C30 also can be accessed locally with a computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 78: Configure Serial Communication

    3.7.1 Configure serial communication A computer with an RS232 port and a serial cable are required. To use the RS485 port at the back of the relay, a GE Digital Energy F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 79: Configure Ethernet Communication

    11. Click OK when the relay order code has been received. The new device is added to the Site List window (or Online window) located in the top left corner of the main EnerVista UR Setup window. The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the C30 section to begin communications.
  • Page 80: Automatic Discovery Of Ur Devices

    • Ethernet port (outlined here) • 3.8.1 Connect to the C30 in EnerVista For information on using the EnerVista software, see the Interfaces chapter. To access the relay in EnerVista: Open the Settings > Product Setup > Display Properties window as shown. The window opens with a status indicator on the lower left of the EnerVista UR Setup window.
  • Page 81: Use Quick Connect Via The Front Panel Rs232 Port

    Connect a nine-pin to nine-pin RS232 serial cable to the computer and the front panel RS232 port. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista DVD or online from http://www.gedigitalenergy.com/multilin). See the software installation section if not already installed.
  • Page 82: Use Quick Connect Via A Rear Ethernet Port

    3.8.3 Use Quick Connect via a rear Ethernet port To use the Quick Connect feature to access the C30 from a computer through Ethernet, first assign an IP address to the relay using the front panel keyboard. Press the key until the menu displays.
  • Page 83 CHAPTER 3: INSTALLATION CONNECT TO THE C30 connections window. Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-49...
  • Page 84 CHAPTER 3: INSTALLATION Click the “Use the following IP address” box. Enter an IP address with the first three numbers the same as the IP address of the C30 relay and the last number different (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the C30 (in this example, 255.0.0.0).
  • Page 85 If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been disconnected from the C30 relay. Start the Internet Explorer software. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-51...
  • Page 86 Click the Quick Connect button to open the window. Select the Ethernet interface and enter the IP address assigned to the C30, then click the Connect button. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Connect”...
  • Page 87: Set Up Cybersentry And Change Default Password

    If using EnerVista, navigate to Settings > Product Setup > Security. Change the Local Administrator Password, for example. It is strongly recommended that the password for the Administrator be changed from the default. Changing the passwords for the other three roles is optional. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 3-53...
  • Page 88 SET UP CYBERSENTRY AND CHANGE DEFAULT PASSWORD CHAPTER 3: INSTALLATION Figure 3-58: Changing the default password 3-54 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 89: Interfaces

    The EnerVista UR Setup software is provided with every C30. This chapter outlines the EnerVista software interface features. The EnerVista UR Setup Help File also provides details for getting started and using the software interface.
  • Page 90: Event Viewing

    IP Address IP Subnet Mask IP Routing When a settings file is loaded to a C30 that is in-service, the following sequence occurs: The C30 takes itself out of service. The C30 issues a UNIT NOT PROGRAMMED major self-test error.
  • Page 91: Settings Templates

    The settings template mode allows the user to define which settings are visible in the EnerVista software. Settings templates can be applied to both settings files (settings file templates) and online devices (online settings templates). The functionality is identical for both purposes. Settings files conversion from previous firmware versions is supported. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 92 By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of the settings window also indicates that the EnerVista software is in EDIT mode. The following example shows the phase time overcurrent settings window in edit mode. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 93 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup window. Select the Template Mode > Password Protect Template option. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 94 Viewing the settings in template mode also modifies the settings menu, showing only the settings categories that contain editable settings. The effect of applying the template to a typical settings menu is shown as follows. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 95 Select an installed device or settings file on the left side of the EnerVista UR Setup window. Right-click and select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 96: Secure And Lock Flexlogic Equations

    Click the Save button to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic equation. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 97 Right-click the setting file in the offline window area and select the Edit Settings File Properties item. The window opens. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 98: Settings File Traceability

    When a settings file is transferred to a C30 device, the date, time, and serial number of the C30 are sent back to EnerVista UR Setup and added to the settings file on the local computer. This information can be compared with the C30 actual values at any later date to determine if security has been compromised.
  • Page 99 With respect to the figure, the traceability feature is used as follows. The transfer date of a settings file written to a C30 is logged in the relay and can be viewed in the EnerVista software or the front panel display. Likewise, the transfer date of a settings file saved to a local computer is logged in the EnerVista software.
  • Page 100: Front Panel Interface

    For example, for 127.0.0.1, press 127, then •, then 0, then •, then 0, then •, then 1. To save the address, press key. ENTER The figure shows the sequence to use to enter a setting. Subsequent sections provide more detail. 4-12 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 101: Menu Navigation

    Default values are indicated in this instruction manual in mixed case. In the example shown here, the default access level is Restricted. Highest level Lowest level (setting value)  SETTINGS  SECURITY ACCESS LEVEL:    PRODUCT SETUP  Restricted   SETTINGS  FLEXLOGIC C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 4-13...
  • Page 102: Changing Settings

    While at the maximum value, pressing the up arrow again allows the setting selection to continue VALUE upward from the minimum value. The down arrow decrements the displayed value by the step value, down to VALUE 4-14 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 103: Faceplate

    4.2.6.1 Enhanced faceplate The front panel consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user- programmable pushbuttons. The faceplate is hinged to allow access to the removable modules. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 4-15...
  • Page 104 Small user-programmable User-programmable Keypad (control) pushbuttons 1 to 7 pushbuttons 1 to 12 827801A . The following figure shows the vertical arrangement of the faceplate panel for relays ordered with the vertical option. 4-16 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 105: Led Indicators

    SETTINGS  INPUT/OUTPUTS  RESETTING keys are used by the breaker control feature. USER Figure 4-19: Typical LED panel for enhanced faceplate 842811A1.CDR The status indicators in the first column are as follows: C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 4-17...
  • Page 106 • NEUTRAL/GROUND — This LED indicates that neutral or ground was involved In the C30, only the OTHER indicator is applicable and indicates that a digital element was involved. NOTE The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user- defined.
  • Page 107 User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. See the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 4-19...
  • Page 108: Custom Led Labeling

    EnerVista UR Setup software is installed and operational • The C30 settings have been saved to a settings file • The UR front panel label cutout sheet (GE part number 1006-0047) has been downloaded from http://www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed • Small-bladed knife To create custom LED labels for the enhanced front panel display: Start the EnerVista UR Setup software.
  • Page 109 NOTE The label package shipped with every C30 contains the three default labels, the custom label template sheet, and the label removal tool. If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match them.
  • Page 110 Bend the tab at the center of the tool tail as shown. To remove the LED labels from the C30 enhanced front panel and insert the custom labels: Use the knife to lift the LED label and slide the label tool underneath. Ensure that the bent tabs are pointing away from the relay.
  • Page 111 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown. To remove the user-programmable pushbutton labels from the C30 enhanced front panel and insert the custom labels: Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown. Ensure that the bent tab points away from the relay.
  • Page 112 CHAPTER 4: INTERFACES label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the 4-24 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 113 The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. Remove the clear Lexan Front Cover (GE part number: 1501-0014). Push in...
  • Page 114: Breaker Control

    Microsoft Word 97 or later software for editing the template • 1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE part number: 1516-0069), and a custom module cover (GE part number: 1502-0015) To customize the display: Open the LED panel customization template with Microsoft Word.
  • Page 115: Change Passwords

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the C30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 116: Invalid Password Entry

    By default, when an incorrect Command or Setting password has been entered via the faceplate interface three times within five minutes, the FlexLogic operand is set to “On” and the C30 does not allow settings or command LOCAL ACCESS DENIED level access via the faceplate interface for five minutes.
  • Page 117: Logic Diagrams

    FLEXLOGIC OPERAND FUNCTION TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 4-29...
  • Page 118 LOGIC DIAGRAMS CHAPTER 4: INTERFACES 4-30 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 119: Settings

      USER-PROGRAMMABLE See page 5-85   LEDS  USER-PROGRAMMABLE See page 5-89   SELF TESTS  CONTROL See page 5-89   PUSHBUTTONS  USER-PROGRAMMABLE See page 5-91   PUSHBUTTONS C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 120 See page 5-151    VIRTUAL OUTPUTS See page 5-154    RESETTING See page 5-154    DIRECT INPUTS See page 5-155    DIRECT OUTPUTS See page 5-155   C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 121: Overview

    The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to the dropout state (logic 0). This can happen when the element is in the operate state if the reset delay time is not 0. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 122: Product Setup

    To reset the unit after a lost password: Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email account. Customer service provides a code to reset the relay to the factory defaults.
  • Page 123 When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the C30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 124 When an original password has already been used, enter it in the Enter Password field and click the Send Password to Device button. Re-enter the password in the Confirm Password field. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 125 INVALID ATTEMPTS BEFORE LOCKOUT The C30 provides a means to raise an alarm upon failed password entry. If password verification fails while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is asserted.
  • Page 126 When this timer expires, local setting access is ACCESS AUTH TIMEOUT immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer updates every five seconds. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 127 The EnerVista security system allows an administrator to manage access privileges of multiple users of EnerVista. It is disabled by default to allow the administrator to access EnerVista software immediately after installation. When security is disabled, all users have administrator access. GE recommends enabling the EnerVista security before placing the device in service.
  • Page 128 Check the Enable Security check box in the lower-left corner to enable the security management system. If you force password entry by using this feature, ensure that you know the Administrator password. If you do not know the password and are locked out of the software, contact GE Digital Energy for the default password NOTE or a UR device.
  • Page 129 The EnerVista security management system must be enabled (the Enable Security check box is enabled) To modify user privileges: Select the Security > User Management item from the top menu to open the user management window. Locate the username in the User field. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-11...
  • Page 130 Click OK to save the changes. 5.3.1.4 CyberSentry security The EnerVista software provides the means to configure and authenticate the C30 access using either a server or the device. Access to functions depends on user role. The login screen of EnerVista has two options for access to the C30, these being Server and Device authentication.
  • Page 131 In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer), as login accounts and the associated passwords are stored on the C30 device. In this case, access is not user-attributable. In cases where user-attributable access is required, especially for auditable processes for compliance reasons, use server authentication (RADIUS) only.
  • Page 132 PRODUCT SETUP CHAPTER 5: SETTINGS Figure 5-2: CyberSentry security panel For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following. 5-14 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 133 Authentication method used by RADIUS EAP-TTLS EAP-TTLS EAP-TTLS Administrator Authentication server. Currently fixed to EAP-TTLS. Method Timeout Timeout in seconds between re- 9999 Administrator transmission requests Retries Number of retries before giving up 9999 Administrator C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-15...
  • Page 134 Text The specified password-protected. All RADIUS users are Password following Me1# role and password-protected. Requirements password Administrator, section earlier section for except for in this chapter requireme Supervisor, where it is only itself 5-16 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 135 This role also has the ability to forcefully log off any other role and clear the security event log. This role can also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-17...
  • Page 136 • Observer — This role has read-only access to all C30 settings. This role allows unlimited concurrent access but it has no download access to any files on the device. Observer is the default role if no authentication has been done to the device.
  • Page 137 Example: If this setting is enabled and an attempt is made to change settings or upgrade the firmware, the UR device denies the settings changes or denies upgrading the firmware. If this setting is disabled, the UR device accepts settings changes and firmware upgrade. This role is disabled by default. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-19...
  • Page 138 RADIUS server. Once both the RADIUS server and the parameters for connecting the UR to the server have been configured, you can choose Server authentication on the login screen of EnerVista. 5-20 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 139 — 255 chars maximum, but in the security log it is truncated to 20 characters Username — Device IP address IP address — 16 bit unsigned, of type format F617 Role Enumeration Role None Administrator Supervisor Engineer Operator Factory C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-21...
  • Page 140: Display Properties

    — If the keypad is inactive for a period of time, the relay automatically reverts to a default DEFAULT MESSAGE TIMEOUT message. The inactivity time is modified using this setting to ensure that messages remain on the screen long enough during programming or reading of actual values. 5-22 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 141: Clear Relay Records

    Some customers prefer very low currents to display as zero, while others prefer the current to display even when the value reflects noise rather than the actual signal. The C30 applies a cut-off value to the magnitudes and angles of the measured currents.
  • Page 142: Communications

    19200 28800, 33600, 38400, 57600, 115200 bit/s RS485 COM2 PARITY: Range: None, Odd, Even  Even RS485 COM2 RESPONSE Range: 0 to 1000 ms in steps of 10  MIN TIME: 0 ms 5-24 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 143 5.3.4.3 Ethernet network topology The C30 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND operation performed between their respective IP address and mask produces a different result.
  • Page 144 In this configuration, P3 uses the IP and MAC addresses of P2. Figure 5-5: Multiple LANs, with redundancy Public Network SCADA EnerVista Software LAN1 LAN2 LAN2 ML3000 ML3000 ML3000 IP1/ IP2/ IP2/ MAC2 MAC2 MAC1 Redundancy mode 859709A4.vsd 5-26 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 145 PRT2 PRP MCST ADDR: Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF  01-15-4E-00-01-00  NETWORK PORT 3 PRT3 IP ADDRESS: Range: standard IPV4 address format   127.0.0.1 PRT3 SUBNET IP MASK: Range: standard IPV4 address format  255.0.0.0 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-27...
  • Page 146 2 is performed. The delay in switching back ensures that rebooted switching devices connected to the C30, which signal their ports as active prior to being completely functional, have time to completely initialize themselves and become active. Once port 2 is active again, port 3 returns to standby mode.
  • Page 147 In this mode, Port 3 uses the MAC, IP address, and mask of Port 2. 5.3.4.7 Routing SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IPv4 ROUTE TABLE 1(6)  IPv4 ROUTE TABLE DEFAULT IPv4 ROUTE   C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-29...
  • Page 148 The routing table configuration is available on the serial port and front panel. This is a deliberate decision, to avoid loss of connectivity when remotely configuring the C30. By default, the value of the destination field is 127.0.0.1 for all static routes (1 to 6). This is equivalent to saying that the static routes are not configured.
  • Page 149 The configuration before release 7.10 was as follows: • PRT1 IP ADDRESS = 10.1.1.2 PRT1 SUBNET IP MASK = 255.255.255.0 PRT1 GWY IP ADDRESS = 10.1.1.1 PRT2 IP ADDRESS = 10.1.2.2 PRT2 SUBNET IP MASK = 255.255.255.0 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-31...
  • Page 150 This allows the EnerVista UR Setup software to be used on the port. UR devices operate as Modbus slave devices only. For more information on the protocol, including the memory map table, see the UR Series Communications Guide. 5-32 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 151 0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change takes effect when the C30 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
  • Page 152 Range: 0 to 100000000 in steps of 1  DEADBAND: 30000 DNP PF DEFAULT Range: 0 to 100000000 in steps of 1  DEADBAND: 30000 DNP OTHER DEFAULT Range: 0 to 100000000 in steps of 1  DEADBAND: 30000 5-34 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 153  COMMUNICATIONS  PROTOCOL multiple DNP masters (usually an RTU or a SCADA master station). Since the C30 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the C30 at one time.
  • Page 154 PRODUCT SETUP CHAPTER 5: SETTINGS The C30 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which the C30 can connect. The settings follow. SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL  DNP NETWORK CLIENT ADDRESSES ...
  • Page 155 DNP TCP connection for greater than the time specified by this setting, the connection is aborted by the C30. This frees up the connection to be re-used by a client. Any change takes effect after cycling power to the relay.
  • Page 156 Appendix A for the range of assignable parameters. Changes to the DNP / IEC 60870-5-104 point lists take effect when the C30 is restarted. The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off”...
  • Page 157 EnerVista setup for IEC 61850 The EnerVista UR Setup software provides the interface to configure C30 settings for the IEC 61850 protocol. This section describes this interface. The software also supports import and export of IEC 61850 Substation Configuration Language (SCL) files as documented in the UR Series Communications Guide.
  • Page 158 Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the connected C30. This SCD file contains all the settings in the UR at the time of the file request, both those that are mapped into the IEC 61850 information model (that is, the "public"...
  • Page 159 Default: TEMPLATE The value entered sets the IED name used by IEC 61850 for the C30. An IED name unique within the network must be entered for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character.
  • Page 160 This setting sets the LN Prefix of logical node GGIO4 that is described in the GGIO4 section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter. 5-42 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 161 Default: 0 This data attribute is provided by the protocol to make changes to the settings of the C30 apparent to clients. The Substation Configuration Tool and UR Setup software advance the value of paramRev each time any setting changes.
  • Page 162 A.3; the UR always uses the ASN.1 Basic encoding rules (as specified in ISO/IEC 8825-1) as specified in IEC 61850-8-1:2004 and as optional in IEC 61850-8-1:2011 clause A.3. So do not try to configure the UR for fixed-offset TxGOOSE. 5-44 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 163 When set to Disabled, no GOOSE messages are published on C30 Ethernet port 1, and any GOOSE messages received on port 1 are ignored. When set to Enabled, all enabled GOOSE messages are published on C30 Ethernet port 1, and any GOOSE messages received on port 1 are listened to.
  • Page 164 32768 to 41151 for GOOSE Type 1A (Trip messages). Some subscribers can process messages in the Type 1A range faster than messages in the Type 1 range. The standard reserves the default value (0) to indicate lack of configuration. The standard strongly recommends unique, source-orientated APPIDs within a given system. 5-46 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 165 RxGOOSE assumes that connectivity is lost. FlexLogic operands (for example, RxGOOSE1 On, RxGOOSE1 Off) reflect the status of each RxGOOSE connectivity. RxGOOSE connectivity of an RxGOOSE with non-zero MAC address is also considered lost after the C30 finishes restart until a message is received. When RxGOOSE connectivity is lost, a common RxGOOSE Fail self-test activates.
  • Page 166 RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry needs to be an ACSI ObjectReference to the publishing control block in the format: <LDName>/LLN0.<GoCBName> 5-48 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 167 <GoCBName> is the name of the publishing control block. The C30 translates the ACSI format required for this setting to the MMS format used in GOOSE messages: <LDName>/LLN0$GO$<GoCBName> If the publisher is a UR 7.3x series device, <LDName> is the value of the publisher's Master functional ldName setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master".
  • Page 168 RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the publisher. The following choices are available: – "On" value defaults the input to logic 1 – "Off" value defaults the input to logic 0 5-50 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 169 This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. The full operand name is the value of this setting appended with "Intermediate," "On," "Off," or "Bad." This descriptive text also appears in the SCL files associated with the C30. RxGOOSE DPS1 RxGOOSE...
  • Page 170 Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Analog Inputs > RxGOOSE Analog Input1 to access the settings for the first RxGOOSE Boolean. The settings and functionality for the others are similar. Figure 5-16: RxGOOSE Analog Inputs panel 5-52 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 171 Range: 0.000 to 1000000000.000 in steps of 0.001 Default: 1.000 This setting specifies the per-unit base value for other C30 features to use with the RxGOOSE Analog1 operand. A FlexElement for instance subtracts two quantities after converting their values to integers rescaled to a common base, the common base being the largest of the base values of the two quantities.
  • Page 172 Also, the control block can be configured to send integrity reports containing the present value of all members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not read and acknowledged by the client to be retransmitted. 5-54 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 173 Control blocks and data sets can be pre-configured by sending the C30 a CID file. See the UR Series Communications Guide for details. EnerVista UR Setup also can be used to select the data set members and to pre-configure the control blocks.
  • Page 174 Range: The check box for an individual bit can be enabled or not Default: All bits true The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The options are as follows: – sequence-number 5-56 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 175 64 members. Any data set can be used simultaneously by any number of TxGOOSE elements and/or by any number of Configurable Report elements. UR Setup software can configure any FlexLogic operands and any FlexAnalog operands as members. Figure 5-19: IEC 61850 DataSets C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-57...
  • Page 176 ("instMag" in the following figure), there is a deadbanded value ("mag" in the figure), which is updated with the present value only when the difference between the two exceeds the deadband setting (db in the figure). Changes to this deadbanded value trigger transmissions when included in GOOSE and report data sets. 5-58 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 177 Navigate to Settings > Communications > IEC 61850 > System Setup > Breakers > Breaker 1 to access the settings that configure the IEC 61850 protocol interface with the first breaker control and status monitoring element. The settings and functionality for the others are similar. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-59...
  • Page 178 SelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of either BkrCSWI1.Pos or Bkr0XCBR1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-interlocking. 5-60 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 179 This setting specifies the maximum time between an operate command to breaker 1 via BkrCSWI1.Pos until BkrCSWI1.Pos.stVal enters the commanded state. The command terminates if the commanded state is not reached in the set time. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-61...
  • Page 180 If a SelectWithValue or Operate service with ctlVal false and with Check.Interlock-check true is requested of DiscCSWI1.Pos or Disc0XSWI1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-interlocking. 5-62 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 181 > System Setup section later. These signals force a disconnect switch trip or close control while the operand selected by setting XSWI1 ST.LOC OPERAND is not active. "sbo" here is select-before-operate. Enhanced security means that the C30 reports to the client the disconnect switch 1 position the end of the command sequence.
  • Page 182 UR reboot immediately following the receipt of a valid CID file. This setting is not mapped into the IEC 61850 information model, but sets the value of SettingControl element attribute actSG in SCL files. 5-64 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 183 This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo" here is select-before-operate. Enhanced security means that the C30 reports to the client the breaker 1 position at the end of the command sequence.
  • Page 184 Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO1 to access the settings for GGIO1. Figure 5-26: IEC 61850 GGIO1 panel 5-66 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 185 Selects the control model for Virtual Input 2, and so on. GGIO4 GGIO4 is a UR feature that allows any of up to 32 UR FlexAnalog operands to be user-mapped to an IEC 61850 information model data attribute. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-67...
  • Page 186 <LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible floating point number. 5-68 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 187 NUMBER: 80 The C30 contains an embedded web server and can display pages in a web browser. The web pages are organized as a series of menus that can be accessed starting at the C30 “Main Menu.” Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on.
  • Page 188 CHAPTER 5: SETTINGS The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the C30 over a network. The C30 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the C30 contains a list and description of all available files (event records, oscillography, and so on).
  • Page 189 0.0.0.0 The C30 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to which the C30 can connect. A maximum of two simultaneous connections are supported at any given time.
  • Page 190 Modbus register address. The default setting value of “0” is considered invalid. Fast exchanges (50 to 1000 ms) are generally used in control schemes. The C30 has one fast exchange (exchange 1) and two slow exchanges (exchange 2 and 3).
  • Page 191 PTP, or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs and none of IRIG-B, PTP, or SNTP is active, the C30 sets the invalid bit in the time stamp of a time-tagged message.
  • Page 192 Spontaneous transmission occurs as a response to cyclic Class 2 requests. If the C30 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the control field of the response).
  • Page 193 INFORMATION NUMBER (INF) as defined in IEC 60870-103. — This is the cyclic period used by the C30 to decide when a measurand ASDU is included in a SCAN TIMEOUT (SCAN TOUT) response. The measurand is sent as response to a Class 2 request when the corresponding timeout expires. The default value 0 means 500 ms.
  • Page 194 FlexAnalog operands. The measurands sent are voltage, current, power, power factor, and frequency. If any other FlexAnalog is chosen, the C30 sends 0 instead of its value. Note that the power is transmitted in KW, not W. Measurands are transmitted as ASDU 3 or ASDU 9 (type identification value set to measurands I, respectively measurands II).
  • Page 195: Modbus User Map

    Commands are received as General Command (Type Identification 20). The user can configure the action to perform when an ASDU command comes. A list of available mappings is provided on the C30. This includes 64 virtual inputs (see the following table). The ON and OFF for the same ASDU command can be mapped to different virtual inputs.
  • Page 196: Real-Time Clock

    The clock is updated by all sources active in the device. This means that whenever a time synchronization message is received through any of the active protocols, the C30 clock updates. However, given that IEC 60870-5-103, IEC 60870-5- 104, Modbus, and DNP are low-accuracy time synchronization methods, avoid their use for synchronization when better accuracy time protocols, such as IRIG-B, PTP, and SNTP, are active in the system.
  • Page 197 1588 software option at the time of ordering. See the Order Codes section in chapter 2 for details. The C30 supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified in IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet network that implements PP.
  • Page 198 Except in unusual cases, the two fibers are of essentially identical length and composition, so make this setting zero. 5-80 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 199 The C30 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the C30 can obtain clock time over an Ethernet network. The C30 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a dedicated product using a GPS receiver.
  • Page 200: Oscillography

     2:00 The C30 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B signals. UTC time is provided by SNTP servers. The real-time clock (RTC) and timestamps reported in historical records and communication protocols can be incorrect if the Local Time settings are not configured properly.
  • Page 201 These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available in a given relay depend on • the type of relay, C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-83...
  • Page 202: Data Logger

    For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of channels for a shorter period. The relay automatically partitions the available memory between the channels in use. The following table outlines examples of storage capacities for a system frequency of 60 Hz. 5-84 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 203: User-Programmable Leds

    DATA LOGGER CONFIG selected to “Off” without overwriting old data. 5.3.9 User-programmable LEDs 5.3.9.1 Menu SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  USER-PROGRAMMABLE  LED TEST See below   LEDS  C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-85...
  • Page 204 The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL setting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. 5-86 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 205 2. When stage 2 is completed, stage 3 starts automatically. The test can be cancelled at any time by pressing the pushbutton. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-87...
  • Page 206 LED 19 operand LED 8 operand LED 20 operand LED 9 operand LED 21 operand LED 10 operand LED 22 operand LED 11 operand LED 23 operand LED 12 operand LED 24 operand 5-88 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 207: User-Programmable Self-Tests

    These are user-programmable and can be used for various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-programmable displays. The location of the control pushbuttons are shown in the following figures. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-89...
  • Page 208 CHAPTER 5: SETTINGS Figure 5-31: Control pushbuttons (enhanced faceplate) Control pushbuttons 842813A1.CDR An additional four control pushbuttons are included on the standard faceplate when the C30 is ordered with the 12 user- programmable pushbutton option. Figure 5-32: Control pushbuttons (standard faceplate) STATUS...
  • Page 209: User-Programmable Pushbuttons

     EVENTS: Disabled The C30 is provided with this optional feature, specified as an option at the time of ordering. Using the order code for your device, see the order codes in chapter 2 for details. User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered with the relay.
  • Page 210 The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the pushbutton. This allows the user-programmable pushbuttons to properly operate during power cycling events and various system disturbances that can cause transient assertion of the operating signals. NOTE 5-92 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 211 PUSHBTN 1 SET PUSHBTN 1 RESET — This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front panel PUSHBTN 1 LOCAL pushbuttons. This locking functionality is not applicable to pushbutton autoreset. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-93...
  • Page 212 “High Priority” or “Normal.” MESSAGE — If this setting is enabled, each pushbutton state change is logged as an event into the event PUSHBUTTON 1 EVENTS recorder. The figures show the user-programmable pushbutton logic. 5-94 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 213 PUSHBUTTON ON pushbuttons logic sheet 2, 842024A2 SETTING Reset Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER 200 ms FLEXLOGIC OPERAND PUSHBUTTON 1 ON 842021A3.CDR C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-95...
  • Page 214: Flex State Parameters

    16 states are readable in a single Modbus register. The state bits can be configured so that all states of interest are available in a minimum number of Modbus registers. 5-96 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 215: User-Definable Displays

    Range: up to 20 alphanumeric characters  DISP 1 ITEM 1 Range: 0 to 65535 in steps of 1   DISP 1 ITEM 5: Range: 0 to 65535 in steps of 1  C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-97...
  • Page 216 If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different. 5-98 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 217: Direct Inputs And Outputs

    UR-series relay are not being received back by the relay. • (direct device offline). These FlexLogic operands indicate that direct output DIRECT DEVICE 1 OFF DIRECT DEVICE 16 OFF messages from at least one direct device are not being received. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-99...
  • Page 218 64 kbps Channel 1 128 kbps Channel 1 128 kbps Channel 1 64 kbps, 128 kbps Channel 2 64 kbps, 128 kbps Channel 1 64 kbps, 128 kbps Channel 2 64 kbps, 128 kbps 5-100 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 219 UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional input and output and programmable logic requirements. The two IEDs are connected via single-channel digital communication cards as shown in the figure.
  • Page 220 DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 4: DIRECT OUTPUT DEVICE ID: “4” DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” 5-102 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 221 A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2 constitute a first ring, while IEDs 2 and 3 constitute a second ring). Figure 5-42: Single-channel open loop configuration UR IED 1 UR IED 2 UR IED 3 842714A1.CDR C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-103...
  • Page 222 IED 2 to IED 3: 0.2 of power system cycle The two communications configurations can be applied to both permissive and blocking schemes. Take speed, reliability, and cost into account when selecting the required architecture. 5-104 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 223 EVENTS: Disabled The C30 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 224: Teleprotection

    “3” (three-terminal system), NUMBER OF CHANNELS NUMBER OF TERMINALS set the to “2.” For a two-terminal system, the can set to “1” or “2” (redundant NUMBER OF CHANNELS NUMBER OF CHANNELS channels). 5-106 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 225: Installation

    5.4 Remote resources 5.4.1 Remote resources configuration When the C30 is ordered with a process card module as a part of HardFiber system, an additional Remote Resources menu tree is available in the EnerVista software to allow configuration of the HardFiber system.
  • Page 226: System Setup

    Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the C30 process card and specific Brick. The relay is then configured to measure specific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 227 1. The number of breaker control elements depends on the number of CT/VT modules specified with the C30. The following settings are available for each breaker control element.
  • Page 228 — This setting specifies the interval required to maintain setting changes in effect after an MANUAL CLOSE RECAL1 TIME operator has initiated a manual close command to operate a circuit breaker. — Selects an operand indicating that breaker 1 is out-of-service. BREAKER 1 OUT OF SV 5-110 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 229 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-45: Dual breaker control logic (Sheet 1 of 2) IEC 61850 functionality is permitted when the C30 is in “Programmed” mode and not in local control mode. NOTE C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 230: Flexlogic

    IEC 61850 trip and close commands shown is one protection pass only. To maintain the close/ open command for a certain time, do so on the contact outputs using the "Seal-in" setting, in the Trip Output element, or in FlexLogic. 5-112 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 231 The number of available disconnect switches depends on the number of the CT/VT modules ordered with the C30. — This setting enables and disables operation of the disconnect switch element.
  • Page 232 SWITCH 1 ALARM DELAY pole position tracking operands do not declare a pole disagreement. This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the C30 is in “Programmed” mode and not in local control mode. NOTE 5-114...
  • Page 233 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-47: Disconnect switch logic C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-115...
  • Page 234: Flexlogic Operands

    Figure 5-48: UR architecture overview The states of all digital signals used in the C30 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a set flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 235 Some types of operands are present in the relay in multiple instances, for example contact and remote inputs. These types of operands are grouped together (for presentation purposes only) on the faceplate display. The table lists characteristics of the different types of operands. Table 5-15: C30 FlexLogic operand types Operand type State...
  • Page 236 8BIT SWITCH 1 BIT 7 Bit 7 of eight-bit switch 1 asserted (the most significant bit) 8BIT SWITCH 2 to 8BIT SWITCH 6 Same set of operands as shown for 8 BIT SWITCH 1 5-118 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 237 Same set of operands as shown for LATCH 1 ELEMENT: PID 1 RAISE PID regulator PID 1 LOWER PID 2 RAISE PID 2 LOWER PID 3 RAISE PID 3 LOWER PID 4 RAISE PID 4 LOWER C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-119...
  • Page 238 Contact inputs Cont Ip 2 On (does not appear unless ordered)   Cont Ip 1 Off (does not appear unless ordered) Cont Ip 2 Off (does not appear unless ordered)   5-120 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 239 An LED test has been initiated and has not finished LED test LED INDICATORS: LED USER 1 Asserted when user-programmable LED 1 is on User-programmable LED USER 2 to 48 The operand above is available for user-programmable LEDs 2 through 48 LEDs C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-121...
  • Page 240 The default names are shown in the FlexLogic operands table. The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are listed in the FlexLogic operators table. 5-122 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 241: Flexlogic Rules

    Assigning the output of an operator to a virtual output terminates the equation. A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") can be used once C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-123...
  • Page 242: Flexlogic Evaluation

    4, which is programmed in the contact output section to operate relay H1 (that is, contact output H1). Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and virtual output 4, shown as follows. 5-124 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 243 It is generally easier to start at the output end of the equation and work back towards the input, as shown in the following steps. It is also recommended C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-125...
  • Page 244 It is now possible to check that this selection of parameters produces the required logic by converting the set of parameters into a logic diagram. The result of this process is shown in the figure, which is compared to the logic for virtual output 3 diagram as a check. 5-126 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 245 Now check that the selection of parameters produce the required logic by converting the set of parameters into a logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-127...
  • Page 246 Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be 5-128 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 247: Flexlogic Equation Editor

    Range: Off, any analog actual value parameter  FLEXELEMENT 1 INPUT Range: SIGNED, ABSOLUTE  MODE: SIGNED FLEXELEMENT 1 COMP Range: LEVEL, DELTA  MODE: LEVEL FLEXELEMENT 1 Range: OVER, UNDER  DIRECTION: OVER C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-129...
  • Page 248 — This setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if FLEXELEMENT 1 +IN this setting is set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element does not assert its output operands. 5-130 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 249 HYSTERESIS = % of PICKUP FlexElement 1 OpSig 842705A1.CDR In conjunction with the setting, the element can be programmed to provide two extra FLEXELEMENT 1 INPUT MODE characteristics, as shown in the following figure. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-131...
  • Page 250 DELTA TIME BASE = 1 µs FREQUENCY = 1 Hz BASE PHASE ANGLE  = 360 degrees (see the UR angle referencing convention) BASE POWER FACTOR = 1.00 BASE RTDs BASE = 100°C 5-132 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 251: Non-Volatile Latches

    — This setting characterizes Latch 1 to be Set- or Reset-dominant. LATCH 1 TYPE — If asserted, the specified FlexLogic operands 'sets' Latch 1. LATCH 1 SET — If asserted, the specified FlexLogic operand 'resets' Latch 1. LATCH 1 RESET C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-133...
  • Page 252: Control Elements

    SELECTOR 1 3BIT A1: Range: FlexLogic operand  SELECTOR 1 3BIT A2: Range: FlexLogic operand  SELECTOR 1 3BIT Range: Time-out, Acknowledge  MODE: Time-out SELECTOR 1 3BIT ACK: Range: FlexLogic operand  5-134 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 253 The acknowledging signal must appear within the time defined by the setting after the last SELECTOR 1 TIME-OUT activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-135...
  • Page 254 The selector position pre-selected via the stepping up control input has not been confirmed before the time out SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time 5-136 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 255 STEP-UP 3BIT A0 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-137...
  • Page 256 SETTINGS  CONTROL ELEMENTS  SETTING GROUPS : “Enabled” SETTING GROUPS FUNCTION : “Off” SETTING GROUPS BLK : “SELECTOR 1 POS 2" GROUP 2 ACTIVATE ON : “SELECTOR 1 POS 3" GROUP 3 ACTIVATE ON 5-138 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 257 SELECTOR 1 STP ALARM Off = 0 3-bit acknowledge SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-139...
  • Page 258: Digital Elements

    Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts. The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A). 5-140 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 259 Using the contact input settings, this input is given an ID name, for example, “Cont Ip 1," and is set “On” when the breaker is closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated (EnerVista example shown). C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-141...
  • Page 260: Digital Counters

    Range: Disabled, Enabled  FUNCTION: Disabled  COUNTER 1 NAME: Range: 12 alphanumeric characters  Counter 1 COUNTER 1 UNITS: Range: six alphanumeric characters  COUNTER 1 PRESET: Range: –2,147,483,648 to +2,147,483,647  5-142 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 261 The present accumulated value and captured frozen value with the associated date/time stamp are available as actual values. If control power is interrupted, the accumulated and frozen values are saved into non-volatile memory during the power-down operation. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-143...
  • Page 262: 8-Bit Switches

    This feature allows switching between two input arguments defined by 8 bits each. The bits are specified by FlexLogic operands. The feature could be viewed as an integrated two-position switch for 8 logic signals. Typically this element is applied in conjunction with the Digitizer and 8-bit Comparator features. 5-144 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 263: Pid Regulator

    Range: Enabled, Disabled   REGULATOR FUNCTION: Disabled PID 1 SAMPLE TIME: Range: 0.05 to 30.00 s in steps of 0.01  0.05 s PID 1 PROCESS Range: Off, any FlexAnalog parameter  SIGNAL: Off C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-145...
  • Page 264 Range: FlexLogic operand  PID 1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset PID 1 Range: Enabled, Disabled  EVENTS: Disabled The figure shows a general form of a PID regulator in the s domain. 5-146 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 265 The incremental form of this equation is: Du k   u k   u k 1   – – Eq. 5-2 Dp k   Di k   Dd k   C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-147...
  • Page 266: Inputs/Outputs

    CONTACT INPUT H5a Range: 0.0 to 16.0 ms in steps of 0.5  DEBNCE TIME: 2.0 ms CONTACT INPUT H5a Range: Disabled, Enabled  EVENTS: Disabled   CONTACT INPUT xxx   5-148 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 267 The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user-settable debounce time in order for the C30 to validate the new contact state. In the following figure, the debounce time is set at 2.5 ms;...
  • Page 268: Virtual Inputs

    There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the COMMANDS appropriate input signal is received. 5-150 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 269: Contact Outputs

    This can be done by monitoring an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-151...
  • Page 270 Disabled The C30 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and populates the setting menu accordingly.
  • Page 271 A latching contact H1a is to be controlled from a single virtual output VO1. The contact is to remain closed as long as VO1 is high, and is to remain opened when VO1 is low. Program the relay as follows. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-153...
  • Page 272: Virtual Outputs

    RESET OP RESET OP to identify the source of the command. The setting here RESET OPERAND (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) selects the operand that creates the operand. RESET OP (OPERAND) 5-154 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 273: Direct Inputs And Outputs

    DIR OUT 1 OPERAND 5.8.6.3 Application examples The examples introduced in the earlier Direct Inputs and Outputs section (part of the Product Setup section) are continued here to illustrate usage of the direct inputs and outputs. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-155...
  • Page 274 UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The figure shows that two IEDs are connected via single-channel digital communication cards.
  • Page 275 UR IED 2 UR IED 3 842714A1.CDR In this architecture, Devices 1 and 3 do not communicate directly. Therefore, Device 2 must act as a ‘bridge’. The following settings are applied: UR IEC 1: C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-157...
  • Page 276 Some examples are directional comparison pilot schemes and direct transfer tripping. Note that failures of communications channels affect teleprotection functionality. The teleprotection function must be enabled to utilize the inputs. 5-158 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 277 (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-159...
  • Page 278: Transducer Inputs/Outputs

    DC voltage or temperature. The relay simplifies this process by internally scaling the output from the external transducer and displaying the actual primary parameter. 5-160 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 279: Rtd Inputs

    1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. See the following table for reference temperature values for each RTD type. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-161...
  • Page 280: Dcma Outputs

    DCMA OUTPUT F1 Range: –90.000 to 90.000 pu in steps of 0.001  MIN VAL: 0.000 pu DCMA OUTPUT F1 Range: –90.000 to 90.000 pu in steps of 0.001  MAX VAL: 1.000 pu 5-162 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 281 The setting is entered in per-unit values. The base units are defined in the same manner as the FlexElement base units. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-163...
  • Page 282: Testing

     FUNCTION: Disabled The C30 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode can be in any of three states: Disabled, Isolated, or Forcible.
  • Page 283: Test Mode Forcing

    On regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves as it does when in service. On restart, the setting and the force contact input and force contact output settings revert TEST MODE FORCING to their default states. NOTE C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 5-165...
  • Page 284: Force Contact Outputs

    While the selected operand is Off, the output behaves as it does when in service. On restart, the setting and the force contact input and force contact output settings revert TEST MODE FORCING to their default states. NOTE 5-166 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 285: Actual Values

       RxGOOSE See page 6-5   STATISTICS  DIGITAL COUNTERS See page 6-5    SELECTOR SWITCHES See page 6-6    FLEX STATES See page 6-6   C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 286: Status

    For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0. 6.2 Status 6.2.1 Contact inputs ACTUAL VALUES  STATUS  CONTACT INPUTS  CONTACT INPUTS Cont Ip 1 Range: On, Off    Cont Ip xx Range: On, Off  C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 287: Virtual Inputs

    Range: On, Off  The C30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. 6.2.4 RxGOOSE DPS inputs ACTUAL VALUES ...
  • Page 288: Teleprotection Inputs

    FlexLogic equation for that output. 6.2.8 RxGOOSE status ACTUAL VALUES  STATUS  RxGOOSE STATUS  RxGOOSE STATUS All RxGOOSE Online: Range: Yes, No   C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 289: Rxgoose Statistics

    Range: On, Off  The C30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE All RxGOOSE Online Input.
  • Page 290: Selector Switches

    Range: Disabled, No Signal, Calibrating, Synch’d (No  NO SIGNAL Pdelay), Synchronized Port 3 PTP State: Range: Disabled, No Signal, Calibrating, Synch’d (No  NO SIGNAL Pdelay), Synchronized PTP - IRIG-B Delta: Range: -500,000,000 to +500,000,000 ns  500,000,000 ns C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 291: Direct Inputs

    The UNRETURNED MSG COUNT CRC FAIL values can be cleared using the command. COUNT CLEAR DIRECT I/O COUNTERS values represent the state of each direct input. DIRECT INPUT 1 DIRECT INPUT (32) C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 292: Direct Devices Status

    STATUS: n/a CHANNEL 2 LOST Range: 1 to 65535 in steps of 1  PACKETS: VALIDITY OF CHANNEL Range: n/a, FAIL, OK  CONFIGURATION: FAIL The status information for two channels is shown here. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 293: Remaining Connection Status

    Range: 0 to 4G, blank if PRP disabled   Total Rx Port B: Range: 0 to 4G, blank if PRP disabled  Total Errors: Range: 0 to 4G, blank if PRP disabled  C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 294: Metering

    Range: 0 to 4G, blank if PRP disabled  The C30 is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details is a counter for total messages received (either from DANPs or from SANs) on Port A.
  • Page 295: Transducer Inputs And Outputs

    CHAPTER 6: ACTUAL VALUES RECORDS The C30 is provided with optional GOOSE communications capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE messages sent from other devices.
  • Page 296: Product Information

    6.5 Product information 6.5.1 Model information ACTUAL VALUES  PRODUCT INFO  MODEL INFORMATION  MODEL INFORMATION ORDER CODE LINE 1: Range: standard GE order code format (lines 1 to 4)   C30-A00-AAA-A0A-A0A SERIAL NUMBER: Range: standard GE serial number format ...
  • Page 297: Firmware Revisions

    Range: YYYY/MM/DD HH:MM:SS  2013/09/15 16:41:32 Date and time when the FPGA was built. The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 6-13...
  • Page 298 PRODUCT INFORMATION CHAPTER 6: ACTUAL VALUES 6-14 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 299: Commands And Targets

    The commands menu contains relay directives intended for operations personnel. All commands can be protected from unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash message appears after successfully command entry. COMMAND EXECUTED C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 300: Virtual Inputs

    When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is over- written. The timescale of the entered time is local time, including daylight savings time where and when applicable. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 301: Relay Maintenance

    Although the diagnostic information is cleared before the C30 is shipped from the factory, the user can want to clear the diagnostic information for themselves under certain circumstances. For example, you clear diagnostic information after replacement of hardware.
  • Page 302: Targets Menu

    If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED indicates that the minimal relay settings have not been programmed. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 303: Relay Self-Tests

    Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the C30 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed module (for example, F8L).
  • Page 304 Check Settings • Latched target message: No. • Description of problem: The setting indicates the C30 is not PRODUCT SETUP  INSTALLATION  RELAY SETTINGS programmed. • How often the test is performed: On power up and whenever the PRODUCT SETUP  INSTALLATION  RELAY SETTINGS setting is altered •...
  • Page 305 DIRECT I/O FAILURE: COMM Path Incomplete • Latched target message: No. • Description of problem: A direct device is configured but not connected. • How often the test is performed: Every second. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 306 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the C30 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 307 AC bank crosschecking setting to none, until the Process Bus Failure clears. Once the problem AC bank has been identified, the values from each of the two Bricks can be examined individually by temporarily mapping each to an AC bank with a single origin. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 308 Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output can still be non-functional. 7-10 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 309: Maintenance

    This chapter outlines maintenance of the hardware and software. 8.1 General maintenance The C30 requires minimal maintenance. As a microprocessor-based relay, its characteristics do not change over time. While the C30 performs continual self-tests, it is recommended that maintenance be scheduled with other system maintenance.
  • Page 310: Back Up And Restore Settings

    IID file in the UR device <destination> is the path and file name of the IID file. If omitted, the file is saved as ur.iid in the command window default directory. An example is TFTP 192.168.1.101 GET ur.iid Feeder1.iid C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 311: Restore Settings

    On a computer on the same subnetwork as the UR device, open a SFTP client application, such as WinSCP. Note that TFTP cannot be used here. Use the device's IP address as the host name. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 312: Upgrade Firmware

    EnerVista UR Setup software. 8.3 Upgrade firmware The firmware of the C30 device can be upgraded, locally or remotely, using the EnerVista software. Instructions are outlined here and in the Help file under the topic “Upgrading Firmware.”...
  • Page 313: Upgrade Software

    In EnerVista, click the Device Setup button. The window opens. Expand the entry for the UR device. Click the Read Order Code button. The order code and version of the device are populated to the software. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 314: Replace Modules

    Open the enhanced faceplate to the left once the thumb screw has been removed. This allows for easy access of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the C30. Figure 8-4: Modules inside relay with front cover open (enhanced faceplate) 842812A1.CDR...
  • Page 315: Battery

    For the standard front panel, it needs to be removed in order to access the power supply module, which is typically in the first slot on the left side and blocked by the hinge of the front panel. To remove the front panel, unscrew its bracket C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 316: Replace Battery For Sh/Sl Power Supply

    Unclip the black plastic holder that keeps the battery in place. The plastic clips into the socket at the bottom on both sides. Use a flat-head screwdriver if you cannot unclip the plastic with your fingers. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 317: Dispose Of Battery

    Batteriet er forsynet med indgraveret symboler for hvad batteriet indeholder: kadmium (Cd), bly (Pb) og kviksølv (Hg). Europæiske brugere af elektrisk udstyr skal aflevere kasserede produkter til genbrug eller til leverandøren. Yderligere oplysninger findes på webstedet www.recyclethis.info. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 318 (Cd), ólom (Pb) vagy higany (Hg) tartalomra utaló betűjelzés. A hulladék akkumulátor leadható a termék forgalmazójánál új akkumulátor vásárlásakor, vagy a kijelölt elektronikai hulladékudvarokban. További információ a www.recyclethis.info oldalon. 8-10 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 319 (Cd), chumbo (Pb), ou o mercúrio (hg). Para uma reciclagem apropriada envie a bateria para o seu fornecedor ou para um ponto de recolha designado. Para mais informação veja: www.recyclethis.info. C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL 8-11...
  • Page 320: Clear Files And Data After Uninstall

    +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 8.7 Clear files and data after uninstall Files can be cleared after uninstalling the EnerVista software or UR device, for example to comply with data security regulations.
  • Page 321: A.1 Flexanalog Items

    DCmA input 2 actual value 13508 DCmA Inputs 3 Value DCmA input 3 actual value 13510 DCmA Inputs 4 Value DCmA input 4 actual value 13512 DCmA Inputs 5 Value DCmA input 5 actual value C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 322 RTD input 25 actual value 13577 RTD Inputs 26 Value RTD input 26 actual value 13578 RTD Inputs 27 Value RTD input 27 actual value 13579 RTD Inputs 28 Value RTD input 28 actual value C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 323 PID 1 delta out 42340 PID 1 Setpoint PID 1 setpoint 42342 PID 2 Out PID 2 out 42344 PID 2 Delta Out PID 2 delta out 42346 PID 2 Setpoint PID 2 setpoint C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 324 RxGOOSE Analog12 GOOSE analog input 12 45608 RxGOOSE Analog13 GOOSE analog input 13 45610 RxGOOSE Analog14 GOOSE analog input 14 45612 RxGOOSE Analog15 GOOSE analog input 15 45614 RxGOOSE Analog16 GOOSE analog input 16 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 325: B Radius Server Configuration

    UR device for successful authentication, and the shortname is a short, optional alias that can be used in place of the IP address. client 10.0.0.2/24 { secret = testing123 shortname = private-network-1 In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content. # ########################################################## GE VSAs ############################################################ VENDOR...
  • Page 326 8.2. Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file.
  • Page 327: C.1 Warranty

    C.1 Warranty For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at https://www.gedigitalenergy.com/multilin/warranty.htm...
  • Page 328 5 April 2012 12-3254 1601-0088-Y1 7.0x 30 September 2012 12-3529 1601-0088-Y2 7.0x 11 November 2012 12-3601 1601-0088-Z1 7.1x 30 March 2013 13-0126 1601-0088-AA1 7.2x 1 August 2013 13-0401 1601-0088-AB1 7.3x 7 November 2014 14-1408 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 329: Revision History

    APPENDIX C: MISCELLANEOUS REVISION HISTORY Table C-2: Major changes for C30 manual version AB1 (English) Page Description Updated document throughout and put into new template. Major revision. Updated references to digital inputs/outputs to contact inputs/outputs for consistency Added content for advanced IEC 61850, for example in the Settings and Actual Values chapters...
  • Page 330 REVISION HISTORY APPENDIX C: MISCELLANEOUS C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 331 CONN Connection CONT Continuous, Contact Generator CO-ORD Coordination General Electric Central Processing Unit Ground Cyclic Redundancy Code/Check GNTR Generator CRT, CRNT Current GOOSE General Object Oriented Substation Event Canadian Standards Association Global Positioning System C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 332 Right Blinder MVA_A MegaVolt-Ampere (phase A) Root Mean Square MVA_B MegaVolt-Ampere (phase B) Remote Open Detector MVA_C MegaVolt-Ampere (phase C) Reset MVAR MegaVar (total 3-phase) RSTR Restrained MVAR_A MegaVar (phase A) Resistance Temperature Detector C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 333 Var-hour voltage Phase B voltage Phase B to A voltage Phase B to Ground voltage Phase C voltage Phase C to A voltage Phase C to Ground voltage Variable Frequency VIBR Vibration Voltage Transformer C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 334 ABBREVIATIONS C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 335 ................... 7-6 SNTP port ..................... 5-81 replace ..................... 8-7 TFTP port ....................5-70 Baud rate ....................5-24 Web access ..................5-69 BLOCK setting ..................5-3 Web access port ................5-69 Comm status remaining connections ........6-9 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 336 ................3-53, 5-20 settings ....................5-155 security commands ................7-3 specifications ..................2-16 security overview ................2-2 Direct outputs system logs ..................5-21 application example ..............5-155 clearing counters ................7-2 error messages ..................7-6 settings ....................5-155 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 337 ..................5-23, 7-2 specifications ..................2-13 specifications ..................2-15 timer settings ...................5-129 via EnerVista software ..............4-2 worksheet ..................5-126 EVENTS setting ..................5-3 Force contact inputs ...............5-165 Export settings to file ................8-2 Force contact outputs ..............5-166 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 338 ................7-6, 7-7 Humidity specifications ..............2-21 specifications ..................2-16 Hysteresis ....................5-131 ISO standards ..................2-23 IEC 60870-5-103 protocol Keypad ...................... 4-12 explained ..................... 5-73 settings ....................5-73 Lamp test ....................7-3 Language setting ................5-22 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 339 ..............6-9 Parallel Redundancy Protocol Flex State parameters ..............5-97 actual values ..................6-9 port, close .....................5-33 explained ....................5-29 register entry ..................5-77 settings ....................5-27 settings ....................5-32 specifications ..................2-20 user map ....................5-77 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 340 FlexLogic operands ..............5-122 actual values ..................6-12 setting to clear LEDs and messages ........5-154 firmware revision ................6-13 to factory defaults ................5-4 Restart relay using EnerVista .................. 5-40 using relay ....................7-3 Restore settings ..................8-2 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 341 FlexLogic operands ...............5-122 clearing counters ................7-2 user-programmable ................5-89 FlexLogic operands ...............5-120 Serial number ..............3-1, 4-9, 6-12 logic diagram ...................5-160 Serial ports overview .....................5-158 settings ....................5-24 settings ................5-106, 5-159 specifications ..................2-19 specifications ..................2-16 Server authentication ...............5-12 C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...
  • Page 342 Unexpected restart error ..............7-8 RS422 and fiber interface ............. 3-33 Uninstall ....................8-12 RS422 interface ................. 3-31 Unit not programmed ..............5-107 Wiring diagram ..................3-9 Unit not programmed message ............ 7-6 Wrong transceiver message ............7-8 viii C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL...

Table of Contents