Transducer Inputs And Outputs; Dcma Inputs - GE C30 Instruction Manual

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5 SETTINGS

5.8TRANSDUCER INPUTS AND OUTPUTS


PATH: SETTINGS
TRANSDUCER I/O
 DCMA INPUT F1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Hardware and software is provided to receive signals from external transducers and convert these signals into a digital for-
mat for use as required. The relay will accept inputs in the range of –1 to +20 mA DC, suitable for use with most common
transducer output ranges; all inputs are assumed to be linear over the complete range. Specific hardware details are con-
tained in chapter 3.
Before the dcmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
dcmA input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels
with the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5F transducer module installed in slot F.
The function of the channel may be either "Enabled" or "Disabled". If "Disabled", no actual values are created for the chan-
nel. An alphanumeric "ID" is assigned to each channel; this ID will be included in the channel actual value, along with the
programmed units associated with the parameter measured by the transducer, such as volts, °C, megawatts, etc. This ID is
also used to reference the channel as the input parameter to features designed to measure this type of parameter. The
setting specifies the mA DC range of the transducer connected to the input channel.
DCMA INPUT F1 RANGE
The
DCMA INPUT F1 MIN VALUE
mary units. For example, a temperature transducer might have a span from 0 to 250°C; in this case the
value is "0" and the
VALUE
DCMA INPUT F1 MAX VALUE
span from –20 to +180 MW; in this case the
value "180". Intermediate values between the min and max values are scaled linearly.
VALUE
GE Multilin


DCMA INPUTS

DCMA INPUT F1(W8)
DCMA INPUT F1
FUNCTION: Disabled
DCMA INPUT F1 ID:
DCMA Ip 1
DCMA INPUT F1
UNITS: μA
DCMA INPUT F1
RANGE: 0 to -1 mA
DCMA INPUT F1 MIN
VALUE:
0.000
DCMA INPUT F1 MAX
VALUE:
0.000
and
DCMA INPUT F1 MAX VALUE
value is "250". Another example would be a watts transducer with a
DCMA INPUT F1 MIN VALUE
C30 Controller System
5.8 TRANSDUCER INPUTS AND OUTPUTS
Range: Disabled, Enabled
Range: up to 20 alphanumeric characters
Range: 6 alphanumeric characters
Range: 0 to –1 mA, 0 to +1 mA, –1 to +1 mA, 0 to 5 mA,
0 to 10mA, 0 to 20 mA, 4 to 20 mA
Range: –9999.999 to +9999.999 in steps of 0.001
Range: –9999.999 to +9999.999 in steps of 0.001
settings are used to program the span of the transducer in pri-
value would be "–20" and the
5.8.1 DCMA INPUTS
5
DCMA INPUT F1 MIN
DCMA INPUT F1 MAX
5-129

Advertisement

Table of Contents
loading

Table of Contents