APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 3 of 47)
ADDR
REGISTER NAME
0828
...Repeated for Digital Counter 6
0830
...Repeated for Digital Counter 7
0838
...Repeated for Digital Counter 8
FlexStates (Read Only)
0900
FlexState Bits (16 items)
Element States (Read Only)
1000
Element Operate States (64 items)
User Displays Actuals (Read Only)
1080
Formatted user-definable displays (16 items)
Modbus User Map Actuals (Read Only)
1200
User Map Values (256 items)
Element Targets (Read Only)
14C0
Target Sequence
14C1
Number of Targets
Element Targets (Read/Write)
14C2
Target to Read
Element Targets (Read Only)
14C3
Target Message
Contact Input/Output States (Read Only)
1500
Contact Input States (6 items)
1508
Virtual Input States (8 items)
1510
Contact Output States (4 items)
1518
Contact Output Current States (4 items)
1520
Contact Output Voltage States (4 items)
1528
Virtual Output States (6 items)
1530
Contact Output Detectors (4 items)
Remote Input/Output States (Read Only)
1540
Remote Device States (2 items)
1542
Remote Input States (4 items)
1550
Remote Devices Online
1551
Remote Double-Point Status Input 1 State
1552
Remote Double-Point Status Input 2 State
1553
Remote Double-Point Status Input 3 State
1554
Remote Double-Point Status Input 4 State
1555
Remote Double-Point Status Input 5 State
Platform Direct Input/Output States (Read Only)
15C0
Direct Input States (6 items)
15C8
Direct Outputs Average Message Return Time 1
15C9
Direct Outputs Average Message Return Time 2
15CA
Direct Inputs/Outputs Unreturned Message Count - Ch. 1
15CB
Direct Inputs/Outputs Unreturned Message Count - Ch. 2
15D0
Direct Device States
15D1
Reserved
15D2
Direct Inputs/Outputs CRC Fail Count 1
15D3
Direct Inputs/Outputs CRC Fail Count 2
Field Unit Input/Output States (Read Only)
15E0
Field Unit Contact Input States (3 items)
15E3
Field Unit Contact Input Output Operand States (8 items)
15EB
Field Contact Output Physical States (8 items)
15F3
Field Contact Output Current States (8 items)
15FB
Field Contact Output Physical States (8 items)
1603
Field Shared Input States
1604
Field Shared Input Channel States
1605
Field Shared Input Test States
GE Multilin
RANGE
UNITS
0 to 65535
0 to 65535
---
0 to 65535
0 to 65535
0 to 65535
0 to 65535
---
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 3
0 to 3
0 to 3
0 to 3
0 to 3
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
C30 Controller System
B.4 MEMORY MAPPING
STEP
FORMAT
---
1
F001
---
1
F502
---
---
F200
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
---
F200
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F126
---
1
F605
---
1
F605
---
1
F605
---
1
F605
---
1
F605
---
1
F500
ms
1
F001
ms
1
F001
---
1
F001
---
1
F001
---
1
F500
---
1
F001
---
1
F001
---
1
F001
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
DEFAULT
0
B
0
(none)
0
0
0
0
"."
0
0
0
0
0
0
0
0
0
0 (No)
3 (Bad)
3 (Bad)
3 (Bad)
3 (Bad)
3 (Bad)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
B-11