Contact Outputs - GE C30 Instruction Manual

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5 SETTINGS
a) DIGITAL OUTPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 CONTACT OUTPUT H1
MESSAGE
MESSAGE
MESSAGE
Upon startup of the relay, the main processor will determine from an assessment of the modules installed in the chassis
which contact outputs are available and present the settings for only these outputs.
An ID may be assigned to each contact output. The signal that can
operand (virtual output, element state, contact input, or virtual input). An additional FlexLogic™ operand may be used to
the relay. Any change of state of a contact output can be logged as an Event if programmed to do so.
SEAL-IN
For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A con-
tacts (see the trip circuit example in the Digital elements section). The monitor will set a flag (see the specifications for
Form-A). The name of the FlexLogic™ operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example,
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect oper-
ation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in the
trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the tripping
circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized in the C30 using the
"Cont Op 1"
CONTACT OUTPUT H1 ID:
any suitable FlexLogic™ operand
OUTPUT H1 OPERATE:
"Cont Op 1 IOn"
OUTPUT H1 SEAL-IN:
CONTACT OUTPUT H1 EVENTS:
b) LATCHING OUTPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 CONTACT OUTPUT H1a
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin


CONTACT OUTPUTS

CONTACT OUTPUT H1 ID
Cont Op 1
OUTPUT H1 OPERATE:
Off
OUTPUT H1 SEAL-IN:
Off
CONTACT OUTPUT H1
EVENTS: Enabled
.
CONT OP 1 ION
FlexLogic™ operand to seal-in the contact output as follows:
CONT OP 1 ION
"Enabled"

CONTACT OUTPUTS
OUTPUT H1a ID
L-Cont Op 1
OUTPUT H1a OPERATE:
Off
OUTPUT H1a RESET:
Off
OUTPUT H1a TYPE:
Operate-dominant
OUTPUT H1a EVENTS:
Disabled
C30 Controller System
CONTACT OUTPUT H1
Range: Up to 12 alphanumeric characters
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Disabled, Enabled
a contact output may be any FlexLogic™
OPERATE
CONTACT OUTPUT H1a
Range: Up to 12 alphanumeric characters
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Operate-dominant, Reset-dominant
Range: Disabled, Enabled
5.7 INPUTS AND OUTPUTS
5.7.3 CONTACT OUTPUTS