5.2 PRODUCT SETUP
EXAMPLE 1: EXTENDING THE INPUT/OUTPUT CAPABILITIES OF A UR-SERIES RELAY
Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic
that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such
as the C30, to satisfy the additional input and output and programmable logic requirements. The two IEDs are connected
via single-channel digital communication cards as shown in the figure below.
Figure 5–10: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID:
DIRECT I/O CH1 RING CONFIGURATION:
DIRECT I/O DATA RATE:
For UR-series IED 2:
DIRECT OUTPUT DEVICE ID:
5
DIRECT I/O CH1 RING CONFIGURATION:
DIRECT I/O DATA RATE:
The message delivery time is about 0.2 of power cycle in both ways (at 128 kbps); that is, from device 1 to device 2, and
from device 2 to device 1. Different communications cards can be selected by the user for this back-to-back connection (for
example: fiber, G.703, or RS422).
EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION
A simple interlocking busbar protection scheme could be accomplished by sending a blocking signal from downstream
devices, say 2, 3, and 4, to the upstream device that monitors a single incomer of the busbar, as shown below.
For increased reliability, a dual-ring configuration (shown below) is recommended for this application.
5-58
"1"
"Yes"
"128 kbps"
"2"
"Yes"
"128 kbps"
UR IED 2
UR IED 3
Figure 5–11: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME
C30 Controller System
BLOCK
UR IED 1
UR IED 4
842712A1.CDR