Flex State Parameters; User-Definable Displays - GE C30 Instruction Manual

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
 FLEX STATE
 PARAMETERS
MESSAGE
MESSAGE
MESSAGE
This feature provides a mechanism where any of 256 selected FlexLogic™ operand states can be used for efficient moni-
toring. The feature allows user-customized access to the FlexLogic™ operand states in the relay. The state bits are packed
so that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states
which are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the "Flex States" register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 USER-DEFINABLE
 DISPLAYS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the
USER DISPLAYS
tate text entry and Modbus register data pointer options for defining the user display content.
Once programmed, the user-definable displays can be viewed in two ways.
KEYPAD: Use the MENU key to select the
that only the programmed screens are displayed). The screens can be scrolled using the UP and DOWN keys. The
display disappears after the default message time-out period specified by the

TIES
DEFAULT MESSAGE TIMEOUT
USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the
setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi-
gate the programmed displays.
GE Multilin


FLEX STATE PARAMETERS

PARAMETER
1:
Off
PARAMETER
2:
Off
PARAMETER
3:
Off
PARAMETER 256:
Off


USER-DEFINABLE DISPLAYS

INVOKE AND SCROLL:
Off
 USER DISPLAY
 USER DISPLAY
 USER DISPLAY
 USER DISPLAY 16
menu (between the
TARGETS
USER DISPLAYS
setting.
C30 Controller System
5.2.13 FLEX STATE PARAMETERS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
5.2.14 USER-DEFINABLE DISPLAYS
Range: FlexLogic™ operand
Range: up to 20 alphanumeric characters
1
Range: up to 20 alphanumeric characters
3
Range: up to 20 alphanumeric characters
2
Range: up to 20 alphanumeric characters
and
top-level menus). The sub-menus facili-
ACTUAL VALUES
menu item to access the first user-definable display (note
PRODUCT SETUP
5.2 PRODUCT SETUP
5

DISPLAY PROPER-
INVOKE AND SCROLL
5-53

Advertisement

Table of Contents
loading

Table of Contents