5.6 CONTROL ELEMENTS
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6
5
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
APPLICATION EXAMPLE
Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting
groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1
through 3. The active setting group shall be available as an encoded three-bit word to the external device and SCADA via
output contacts 1 through 3. The pre-selected setting group shall be applied automatically after 5 seconds of inactivity of
the control inputs. When the relay powers up, it should synchronize the setting group to the three-bit control input.
Make the following changes to setting group control in the
SETTING GROUPS FUNCTION:
SETTING GROUPS BLK:
GROUP 2 ACTIVATE ON:
GROUP 3 ACTIVATE ON:
Make the following changes to selector switch element in the
menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:
SELECTOR SWITCH 1
5-98
pre-existing
changed to 4 with
changed to 1 with
position 2
a pushbutton
a 3-bit input
Figure 5–35: ACKNOWLEDGE MODE
"Enabled"
"Off"
"SELECTOR 1 POS 2"
"SELECTOR 1 POS 3"
C30 Controller System
changed to 2 with
a pushbutton

SETTINGS
CONTROL ELEMENTS
"SELECTOR 1 POS 4"
GROUP 4 ACTIVATE ON:
"Off"
GROUP 5 ACTIVATE ON:
"Off"
GROUP 6 ACTIVATE ON:

SETTINGS
CONTROL ELEMENTS
5 SETTINGS
842736A1.CDR
menu:
SETTING GROUPS

SELECTOR SWITCH
GE Multilin