Advertisement

5.5 FLEXLOGIC™
5 SETTINGS
The
setting defines the pickup–dropout relation of the element by specifying the width of the
FLEXELEMENT 1 HYSTERESIS
hysteresis loop as a percentage of the pickup value as shown in the FlexElement™ direction, pickup, and hysteresis dia-
gram.
The
setting specifies the time unit for the setting
. This setting is applicable only if
FLEXELEMENT 1 DT UNIT
FLEXELEMENT 1 dt
is set to "Delta". The
setting specifies duration of the time interval for the
FLEXELEMENT 1 COMP MODE
FLEXELEMENT 1 DT
rate of change mode of operation. This setting is applicable only if
is set to "Delta".
FLEXELEMENT 1 COMP MODE
This
setting specifies the pickup delay of the element. The
setting
FLEXELEMENT 1 PKP DELAY
FLEXELEMENT 1 RST DELAY
specifies the reset delay of the element.