5 SETTINGS

PATH: SETTINGS
PRODUCT SETUP
 DATA LOGGER
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
Table 5–3: DATA LOGGER STORAGE CAPACITY EXAMPLE
SAMPLING RATE
CHANNELS
15 ms
1
8
9
16
1000 ms
1
8
9
16
60000 ms
1
8
9
16
3600000 ms
1
8
9
Changing any setting affecting data logger operation will clear any data that is currently in the log.
NOTE
GE Multilin


DATA LOGGER

DATA LOGGER MODE:
Continuous
DATA LOGGER TRIGGER:
Off
DATA LOGGER RATE:
60000 ms
DATA LOGGER CHNL
1:
Off
DATA LOGGER CHNL
2:
Off
DATA LOGGER CHNL
3:
Off
DATA LOGGER CHNL 16:
Off
DATA LOGGER CONFIG:
0 CHNL x
0.0 DAYS
DAYS
STORAGE CAPACITY
0.1
954 s
0.1
120 s
0.1
107 s
0.1
60 s
0.7
65457 s
0.1
8182 s
0.1
7273 s
0.1
4091 s
45.4
3927420 s
5.6
490920 s
5
436380 s
2.8
254460 s
2727.5
235645200 s
340.9
29455200 s
303
26182800 s
C30 Controller System
5.2 PRODUCT SETUP
5.2.8 DATA LOGGER
Range: Continuous, Trigger
Range: FlexLogic™ operand
Range: 15 to 3600000 ms in steps of 1
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
Range: Not applicable - shows computed data only
5